Winco DGC-2020 User Manual
Page 183

9400200990 Rev B
DGC-2020 Modbus
™ Communication
B-25
Holding
Register
Parameter Range
Read/Write
Supported
Data
Format
Units
42042
Breaker Close Wait Time
0.1 - 600.0
R W
FP
seconds in
increments of
0.1
42044
Sync Time Delay
0.1 - 0.8
R W
FP
seconds in
increments of
0.1
42046
Sync Fail Time Delay
0.1 - 600.0
R W
FP
seconds in
increments of
0.1
42048
Mains Fail Transfer Enable
0-1
R W
0 = Disabled,
1 = Enabled
42050
Gen Breaker Status
0-1
R
0 = Open,
1 = Closed
42052
Mains Breaker Status
0-1
R
0 = Open,
1 = Closed
42054-248 FUTURE
USE
SYNCHRONIZER BIAS CONTROLS
42250-92 RESERVED
42294-498 FUTURE
USE
42500
AVR Correction Pulse Width
0-999
R W
milliseconds * 100 in increments of 1
42502
AVR Correction Pulse Interval
0-999
R W
milliseconds * 100 in increments of 1
42504
AVR Bias Contact Type
0-1
R W
0 = Continuous,
1 = Proportional
42506 RESERVED
42508
Governor Correction Pulse Width
0-999
R W
milliseconds * 100 in increments of 1
42510
Governor Correction Pulse Interval
0-999
R W
milliseconds * 100 in increments of 1
42512
Governor Bias Contact Type
0-1
R W
0 = Continuous,
1 = Proportional
42514 RESERVED
42516-748 FUTURE
USE
BUS CONDITION DETECTION
42750
Gen Sensing Dead Bus Pickup
0-4800
R W
(Volts / 10) in increments of 10
42752
Gen Sensing Dead Bus Time Delay
1-6000
R W
(milliseconds * 100) in increments of 1
42754 RESERVED
42756
Gen Sensing Stable Undervoltage
Pickup
100-12000
R W
(Volts / 10) in increments of 10
42758
Gen Sensing Stable Undervoltage
Dropout
100-12000
R W
(Volts / 10) in increments of 10
42760
Gen Sensing Stable Overvoltage
Pickup
100-12000
R W
(Volts / 10) in increments of 10
42762
Gen Sensing Stable Overvoltage
Dropout
100-12000
R W
(Volts / 10) in increments of 10
42764
Gen Sensing Stable
Underfrequency Pickup
4600-6400
R W
(Hz / 100) in increments of 5
42766
Gen Sensing Stable
Underfrequency Dropout
4600-6400
R W
(Hz / 100) in increments of 5
42768
Gen Sensing Stable Overfrequency
Pickup
4600-6400
R W
(Hz / 100) in increments of 5
42770
Gen Sensing Stable Overfrequency
Dropout
4600-6400
R W
(Hz / 100) in increments of 5
42772
Gen Sensing Fail Time Delay
1-6000
R W
(milliseconds * 100) in increments of 1
42774
Gen Sensing Stable Time Delay
1-6000
R W
(milliseconds * 100) in increments of 1
42776 RESERVED
42778
Bus Sensing Dead Bus Pickup
0-4800
R W
(Volts / 10) in increments of 10
42780
Bus Sensing Dead Bus Time Delay
1-6000
R W
(milliseconds * 100) in increments of 1
42782 RESERVED
42784
Bus Sensing Stable Undervoltage
Pickup
100-12000
R W
(Volts / 10) in increments of 10
42786
Bus Sensing Stable Undervoltage
Dropout
100-12000
R W
(Volts / 10) in increments of 10
42788
Bus Sensing Stable Overvoltage
Pickup
100-12000
R W
(Volts / 10) in increments of 10