beautypg.com

Cleaning pilot and burners, Burner rack, Burner rack removal instructions – Reznor SCE Unit Installation Manual User Manual

Page 34

background image

Form RZ-NA I-SCE, Page 34

31. Cleaning Pilot

and Burners

CAUTION: When

cleaning, wearing eye

protection is

recommended.

29. Vent/Combustion

Air System

32. Spark Ignition

System

Check at least once a year. Inspect all joints, seams and terminal caps. Replace any defective

parts.

30. Burner Rack

Burner Rack Removal Instructions

1. Turn off the gas supply.

2. Turn off the electric supply.

3. Remove control access side panel.

4. Disconnect ignition and flame sensor leads.

5. Mark and disconnect electric valve leads.

6. Uncouple the union in the gas supply.

7. Remove sheetmetal screws in the top corners of the burner rack assembly.

8. Pull "drawer-type" burner rack out of the furnace.
To disassemble the burner rack:

1. Remove Carryover System --

Natural Gas - remove the flash carryover system from the "manifold end" of the burner rack

NOTE: Natural gas burner racks manufactured prior to Series 6 may have a lighter tube carryover

system. Break the lighter tube connection at the orifice and remove the supply tubing, the drip

shield and the lighter tube.

Propane Gas - break the lighter tube connection at the regulator and remove the lighter tube

orifice supply tubing; remove the retaining screws in the drip shield and the shield; remove the

retaining screws and slide out the lighter tube.

2. Pull main burners horizontally away from injection opening and lift out.

3. Remove manifold bracket screws and remove manifold.

4. Remove burner orifices.

5. Remove screws and lift out pilot burner.

Follow the instructions in Paragraph 30 to clean. To re-assemble and replace, reverse the above

procedures being careful not to create any unsafe conditions.

In the event the pilot flame is short and/or yellow, check the pilot orifice for blockage caused by

lint or dust accumulation. Remove the pilot orifice and clean with air pressure. DO NOT REAM

THE ORIFICE. Check and clean the aeration slot in the pilot burner.

Clean the metal sensing probe and the pilot hood with an emery cloth and wipe off the ceramic

insulator. Check the spark gap; spark gap should be maintained to .100". After the pilot is cleaned,

blow any dirt away with compressed air.
Clean main burners and burner orifices using air pressure. Use an air nozzle to blow out scale and

dust accumulation from the burner ports. Alternately blow through the burner ports and the

venturi. Use a fine wire to dislodge any stubborn particles from the burner ports. Do not use

anything that might change the port size.
Clean the burner rack carryover systems with air pressure.

The ignition controller provides the high voltage spark to ignite the pilot service and also acts as

the flame safety device. After ignition of the pilot gas, the controller electronically senses the

pilot flame. A separate solid metal probe in the pilot burner assembly is used to sense the flame.

A low voltage DC electrical signal is imposed on the metal probe which is electrically insulated

from ground. Proper operation of the electronic spark ignition system requires a minimum

flame signal of .2 microamps DC as measured by a microampmeter. When the pilot flame

impinges on the sensing probe, the flame acts as a conduction path to ground. This completes

the DC circuit; the ignition controller responds by energizing the main gas valve.

CAUTION: Due to

high voltage on pilot

spark wire and pilot

electrode, do not touch

when energized. See

Hazard Levels, page 2.

If no spark occurs, check the following:

a) Voltage between blue and white terminals (non-lockout type pilot) and Terminals 2 and 5

(lockout type pilot) on the ignition controller should be at least 20 volts and no higher than

32 volts. Refer to Troubleshooting (Paragraph 36) if no voltage is observed.

b) Short to ground in the high tension lead and/or ceramic insulator.

c) Pilot spark gap should be approximately .100". (See FIGURE 35.)
NOTE: When checking for spark with the pilot burner assembly removed from the burner rack,

the pilot assembly must be grounded to the heater for proper spark.

If the above conditions are normal and no spark occurs, replace the ignition controller.