Sizing gas supply lines – Reznor SCE Unit Installation Manual User Manual
Page 19
Form RZ-NA I-SCE, Mfg #207697 Rev 7,
Page 19
Sizing Gas Supply Lines
Measuring manifold gas pressure cannot be done until the heater is in operation. It is
included in the steps of the "Check-Test-Start" procedure in Paragraph 25. The following
warnings and instructions apply.
For Natural Gas: When the heater leaves the factory, the combination valve is set so that the
outlet gas pressure of a single-stage valve or high fire of a two-stage valve is regulated to
3.5" w.c. Low fire on a two-stage valve is set to 1.8" w.c. Inlet supply pressure to the valve
must be a minimum of 5" w.c. or as noted on the rating plate and a maximum of 14" w.c. NOTE:
Always check the rating plate for minimum gas supply pressure. Minimum supply pressure
requirements vary based on size of burner and the gas control option. Most units require a
minimum of 5" w.c. of natural gas as stated above, but Sizes 350 and 400 with electronic
modulation require a minimum of 6" w.c. natural gas supply pressure. Sizes 300 and 350 with
mechanical modulation require 7" w.c.
For Propane Gas: When the heater leaves the factory, the combination valve is set so that
the outlet gas pressure of a single-stage valve or high fire of a two-stage valve is 10" w.c.
Low fire on a two-stage valve is set to 5" w.c. Inlet pressure to the valve must be a minimum
of 11" w.c. and a maximum of 14" w.c.
Before attempting to measure or adjust manifold gas pressure, the inlet (supply) pressure
must be within the specified range for the gas being used both when the heater is in opera-
tion and on standby. Incorrect inlet pressure could cause excessive manifold gas pressure
immediately or at some future time.
Instructions to Check Valve Outlet (Manifold) Pressure:
1) With the manual valve (on the combination valve) positioned to prevent flow to the main
burners, connect a manometer to the 1/8" pipe outlet pressure tap in the valve. NOTE: A
manometer (fluid-filled gauge) is recommended rather than a spring type gauge due to the
difficulty of maintaining calibration of a spring type gauge.
2) Open the valve and operate the heater. Measure the gas pressure to the manifold. To
measure the low stage pressure on units equipped with a two-stage valve, disconnect the
wire from the "HI" terminal on the valve. (Be sure to reconnect the wire.)
Normally adjustments should not be necessary to the factory preset regulator. If adjustment
is necessary, set pressure to correct settings by turning the regulator screw IN (clockwise) to
increase pressure. Turn regulator screw OUT (counterclockwise) to decrease pressure. Con-
sult the valve manufacturer's literature provided with the furnace for more detailed informa-
tion.
Manifold or Orifice
(Valve Outlet) Pressure
Settings
Capacity of Piping
Cubic Feet per Hour based on 0.3" w.c. Pressure Drop
Specific Gravity for Natural Gas -- 0.6 (Natural Gas -- 1000 BTU/Cubic Ft)
Specific Gravity for Propane Gas -- 1.6 (Propane Gas -- 2550 BTU/Cubic Ft)
Length
Diameter of Pipe
of
1/2"
3/4"
1"
1-1/4"
1-1/2"
2"
Pipe Natural Propan Natural Propan Natural Propan Natural Propan Natural Propan Natural Propan
20'
92
56
190
116
350
214
730
445
1100
671
2100
1281
30'
73
45
152
93
285
174
590
360
890
543
1650
1007
40'
63
38
130
79
245
149
500
305
760
464
1450
885
50'
56
34
115
70
215
131
440
268
670
409
1270
775
60'
50
31
105
64
195
119
400
244
610
372
1105
674
70'
46
28
96
59
180
110
370
226
560
342
1050
641
80'
43
26
90
55
170
104
350
214
530
323
990
604
90'
40
24
84
51
160
98
320
195
490
299
930
567
100'
38
23
79
48
150
92
305
186
460
281
870
531
125'
34
21
72
44
130
79
275
168
410
250
780
476
150'
31
19
64
39
120
73
250
153
380
232
710
433
175'
28
17
59
36
110
67
225
137
350
214
650
397
200'
26
16
55
34
100
61
210
128
320
195
610
372
Note: When sizing supply lines, consider possibilities of future expansion and increased requirements.
Refer to National Fuel Gas Code for additional information on line sizing.