beautypg.com

Optional filter rack and filters, 27a. optional dirty filter switch – Reznor SCE Unit Installation Manual User Manual

Page 32

background image

Form RZ-NA I-SCE, Page 32

FIGURE 32A - Filter

Arrangement

FIGURE 32B - Filter Arrangement FIGURE 32C - Filter Arrangement

Size 400

Sizes 200-350

Sizes

125-

175

27A. Optional Dirty Filter

Switch

The optional dirty filter pressure switch is used to provide warning to the user by energizing

an indicator light on an optional remote console. The light indicates that the filters are in

need of cleaning or changing. The adjustable, single-pole/normally open differential switch

closes when an increase in pressure differential above the setpoint, is sensed across the

filter bank.

This switch is located in the furnace section. After the unit is started, before continuous

operation, the dirty filter switch must be set.

27. Optional Filter

Rack and Filters

Outside Air

Damper CLOSED

Return Air Damper OPEN

Rod for Outside

Air Damper

Set Screw

Outside

Air

Damper

Arm

Return

Air

Damper

Arm

Rod for Return

Air Damper

Damper

Motor

Damper Linkage --

When units are equipped

with dampers, the dampers

are closed during shipment.

When there are both return

air and outside air dampers,

the return damper linkage

must be adjusted prior to use.

1. Loosen the set screw on the return air damper rod at the damper arm.

2. Manually open the return air dampers. While the dampers are open-

ing, the damper rod and arm will automatically move to their correct

positions.

3. Tighten the set screw.

FIGURE 31 - Control Locations for Air Inlet/Damper Options

(1) Outside Air Damper

(2) Return Air Damper

(3) Damper Motor

(4) Potentiometer

NOTE: The illustration is intended to show location

only of various air control accessories and does not

represent suggested combinations of accessories.

OPTIONAL EQUIPMENT
26. Optional Dampers and Controls (See Wiring Diagram supplied with unit)

(5) Potentiometer

(6) Mixed Air Controller

(7) Warmup Control

(8) Remote Potentiometer

Filter racks and filters are factory installed optional equipment on indoor systems. 1" or 2"

disposable, pleated disposable, or permanent filters are available.

Heater

Filters

Metal Fillers

FIGURE Reference for

Size

A

B

C

D

E

F1

F2

Qty of Filters and Fillers

125

20x20 20x20

--

--

--

--

--

32A

150, 175

20x25 20x25

--

--

--

13/16 13/16

200, 225

16x25 16x20 16x25 16x20

--

--

--

250, 300

20x25 20x20 20x25 20x20

--

--

--

32B

350

20x25 20x25 20x25 20x20

--

4-13/16

--

400

16x25 20x25 16x25 20x25 16x25 2-5/8 1-1/16

32C

Filter

and

Filler
Sizes