beautypg.com

Horizontal vent instructions (cont’d) – Reznor SCE Unit Installation Manual User Manual

Page 14

background image

Form RZ-NA I-SCE, Page 14

6-15/16” (176mm)

Concentric

Adapter Box

Double-Wall

Vent Pipe -

Pitch to

Drain

Thimble

Combustion Air Pipe -

Pitch to Drain

3 ft (1M)

minimum

3 ft (1M)

minimum

6 ft (1.8M) minimum

Adjoining Building

Building Projection

Building Overhang

W a l l

Inlet Air

Guard

Exhaust (Vent) Cap

IMPORTANT: Install exhaust cap so the baffles

are positioned at 12:00, 3:00, 6:00, and 9:00 o’clock.

Side View

16” (406mm)

minimum

24” (610mm)

maximum

Concentric

Adapter

Box

Wall

Screened

Exhaust

Cap

Inlet Air

Guard

Combustion Air to heater (seal joints)

Vent (Flue Exhaust) Pipe

from heater (seal joints)

Heater

Distance between the

Concentric Adapter Box

and the Heater

For Maximum Length,

see Table on page 8.

Minimum length is 5 ft (1.5M).

Attach double-vent pipe to vent run no

more than 6” (152mm) from the box. A

taper-type reducer is required.

2” (51mm) if wall is combustible

Attach box to wall with brackets.

One piece of

Double-Wall

Vent Pipe

2” (51mm)

(152

mm)

1” (25mm)

minimum

48”

(1219mm)

maximum

Top View

FIGURE 13 - Installation

of a Typical Separated-

Combustion Unit with

Horizontal Vent and

Combustion Air Pipes

(Option CC6)

completely.
10. Attach the indoor combustion air pipe. If using 6" pipes, attach the single-wall combus-

tion air pipe run to the collar on the concentric adapter box with sheetmetal screws. If using

7” pipe on Sizes 200-400, install a taper type enlarger as illustrated In FIGURE 11, page 11.
Seal joints with tape or sealant.
Installation of the horizontal vent and combustion air system on your separated-combus-

tion unit is complete. Verify compliance with all venting installation requirements, pages

8-11, and FIGURE 13.

HORIZONTAL VENT

INSTRUCTIONS

(cont’d)