Form RZ-NA I-SCE, Mfg #207697 Rev 7,

Page 17

FIGURE 17 - Install Combustion Air Inlet and Vent Terminal

7. On the outside, slide the combustion air inlet

over the vent pipe and fasten the collar to the

combustion air pipe with sheetmetal screws. See

FIGURE 17 . Seal the opening at the top

between the vent pipe and the combustion air

inlet with silicone sealant to prevent water

leakage.
8. Attach the exhaust (vent) cap. Follow the

illustrated instructions in FIGURE 8 , page 9.

FIGURE 18 - Installation of Unit

with Vertical Vent Terminal/

Combustion Air Inlet (Option CC2)

Rear

View

Side V iew

9. Attach the indoor combustion air pipe. Use

sheetmetal screws to attach the single-wall

combustion air pipe run to the collar on the

concentric adapter box.
If using 7” pipe on Sizes 200-400, install a taper

type enlarger as illustrated in FIGURE 11, page

11.
Seal joint with tape or sealant.

Installation of the vertical vent and combustion air system on your separated-

combustion unit is complete. Verify compliance with all venting installation re-

quirements, pages 8-11, and FIGURE 18 below.