21D. Computer

Controlled

Electronic

Modulation

(cont'd)

Is there 24 volts

between Terminal 2 on #1

Time Delay Relay and

Terminal 7?

Go to

Troubleshooting

Chart for heater.

Is there 24 volts

between Terminal 84 and

Terminal 7?

Is the

damper open?

Is there voltage

between Terminal 88 and

Terminal 7?

Is there voltage

between Terminal 4 on

ignition permissive relay and

Terminal 7?

Replace #1 time

delay relay.

Replace ignition

permissive

relay.

Check combustion

damper lower end switch

adjustment. If necessary,

replace end switch.

Is there voltage

between Terminal 87 and

Terminal 7?

Check combustion

damper lower end switch

adjustment. Replace end

switch if necessary.

Place a jumper

across Terminal

86 and Terminal 7.

Did the

damper close?

Replace motor

run time delay

relay.

Replace combustion

damper gear motor.

Replace primary

manifold

pressure switch.

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

NO

YES

YES

NO

Measure manifold

pressure

during burner cycling.

When the

manifold pressure is

BELOW 1.0" w.c., is there a steady

voltage between Terminal 95

and Terminal 7?

Replace secondary

manifold pressure

switch.

While the

burner is cycling, is

there a steady voltage

between Terminal 84 and

Terminal 2?

Replace the

primary manifold

pressure switch.

When the

manifold pressure is

ABOVE 1.5" w.c., is there a steady

voltage between Terminal 95

and Terminal 7?

Replace secondary

manifold pressure

switch.

Is there voltage

between Terminal 4 of the

ignition premissive relay and

Terminal 7?

Replace ignition

permissive

relay.

YES

NO

YES

NO

YES

NO

Symptom - Part 1:

Main burners are inoperative.

Assumes that 24 volts is

available between Terminal 2

and Terminal 7.

General Instructions: For each step,

check to ensure that the wiring is not

defective and that the wiring connec-

tions are secure.

Symptom - Part 2:

Steady call for heat - burner cycles.

Assumes that 24 volts is available between Terminals 11 and 7 and Terminals 2 and 7.

tioner accepts a 4-20 milliamp signal. In the "off" positions, the conditioner accepts a 0-10V

signal. The conditioner converts the signal to the 0 to 20 volt DC current required to control the

modulating valve. The heater functions and is equipped in the same way as described in Para-

graph 21C (Option AG39) except that with computer control the temperatures are selected through

the software and there is no temperature selector or duct sensor.

FIGURE 28 - Troubleshooting Guide for Checking Bypass Combustion Air Damper Safety Circuit on

Model SCE with Option AG39 or AG40