beautypg.com

Horizontal vent instructions, Components required - factory and field – Reznor SCE Unit Installation Manual User Manual

Page 12

background image

Form RZ-NA I-SCE, Page 12

HORIZONTAL VENT

INSTRUCTIONS

Components Required -

Factory and Field

Parts in the Horizontal Vent

Terminal/Combustion Air

Package (Option CC6)

Field-supplied installation

requirements:

• Vent pipes - see requirements, page 8.

• Combustion air pipes - see requirements, page 8.

• Taper-type vent pipe diameter reducers and/or increasers as required.

• Thimble (a thimble is not required if wall is of non-combustible construction).

• Flashing.

• Sheetmetal screws, tape, and sealant as required.

Installation Instructions

for Horizontal Vent Kit

Option CC6

1. Determine the location on the outside wall for the vent terminal. Location must comply

with vent length requirements, Requirement No. 3 on page 8. In most applications, the

terminal would be on a level with the heater mounting height. Allow 1/4" per foot (6mm per

305mm) downward pitch for condensate drain.
The distance of the termination of the horizontal vent from adjacent public walkways, adja-

cent buildings, openable windows, and building openings must be in accordance with local

codes or, in the absence of local codes, must conform with National Fuel Gas Code Z223.2.

Local codes supersede all provisions in these instructions and in the National Fuel Gas

Code. Minimum clearances for the horizontal vent terminal are shown below. Also, select a

location that complies with adjoining building clearances as shown in FIGURE 13, page 14.

Products of combustion can cause discoloring of some building finishes and deterioration of

masonry materials. Applying a clear silicone sealant that is normally used to protect concrete

driveways can protect masonry materials. If discoloration is an esthetic problem re-locate the

vent or install a vertical vent.

2. Install the Vent Pipe and Combustion Air Pipe Runs - Use the type of pipe specified in

Requirement No. 1, page 8. Comply with requirements in Requirement No. 2 and No. 4, page

8, when attaching pipes to the heater.
Seal all joints. Due to the high temperature, do not enclose the exhaust pipe or place pipe

closer than 6" (152 mm) to combustible material. Extend the runs close to the wall location

selected in Step 1. Support pipes as required in Requirement No. 5, page 10.

WARNING: All vent

terminals must be

positioned or located

away from fresh air

intakes, doors and

windows to preclude

combustion products

from entering occupied

space. Failure to comply

could result in severe

personal injury or death

and/or property damage.

Clearances to Horizontal

Vent Terminal

Structure

Minimum Clearances for Vent Terminal

Location (all directions unless specified)

Forced air inlet within 10 ft (3.1M)*

3 ft (0.9M) above

Combustion air inlet of another appliance 6 ft (1.8M)

4 ft (1.2M) horizontally

4 ft (1.2M) below
1 ft (305mm) above

Electric meter, gas meter ** and relief

equipment

U.S. - 4 ft (1.2M) horizontally

Gas regulator **

U.S. - 3 ft (0.9M); horizontally)

Adjoining building or parapet

6 ft (1.8M)

Adjacent public walkways

7 ft (2.1M) above

Grade (ground level)

3 ft (.9M) above***

Door, window, or gravity air inlet (any

building opening)

*Does not apply to the inlet of a direct vent appliance. **Do not terminate the vent directly

above a gas meter or service regulator. *** Consider local snow depth conditions. The vent

must be at least 6” (152mm) higher than anticipated snow depth.

Screened

Exhaust

Assembly,

P/N 53316

Inlet Guard,

P/N 205894

Qty P/N Description

1

205883 Complete Horizontal Vent Kit (Same as Option CC6)

1

205885 Concentric Adapter Box Assembly (See FIGURE 10, page 10.)

1

53316 Screened Exhaust Assembly (illustrated below)

1

205894 Inlet Guard (illustrated below)

4

37661 #10-16 x 1/2" long Screws to attach the inlet guard

2

207232 Brackets for attaching Concentric Adapter Box (See FIGURE 12, page 13.)

1

53335 Tube of High Temperature (450°F) Silicone Sealant