beautypg.com

Horizontal vent instructions (cont’d) – Reznor SCE Unit Installation Manual User Manual

Page 13

background image

Form RZ-NA I-SCE, Mfg #207697 Rev 7,

Page 13

HORIZONTAL VENT

INSTRUCTIONS

(cont’d)

3. Prepare a hole through the outside wall for the 8" (203mm) diameter combustion air

pipe. Outside wall construction thickness should be between 1" (25mm) minimum and 48"

(1143mm) maximum. The larger diameter combustion air pipe serves as clearance for the

vent pipe on non-combustible construction. A thimble may be required depending on wall

construction and/or local codes.
4. Prepare the Concentric Adapter Box
a) Attach the brackets to the box.
Follow the instructions in FIGURE 12 .

b) Attach the outside portion of the combustion air pipe to the box. Determine the length

by measuring the bracket length from box to wall, plus the wall thickness, plus 2" (51 mm).

(The inlet air pipe should extend beyond the outside wall approximately 2" (51mm).)
Attach the inlet air pipe to the collar of the concentric adapter with sheetmetal screws and

seal.
5. Attach the concentric adapter box to the wall. Insert the combustion air pipe through

the wall. Attach the brackets ( FIGURE 12 ) to the wall. On the outside, caulk or flash the

inlet air pipe. Flashing is field-supplied.
6. Position the inlet guard over the end of the combustion air pipe. See FIGURE 13 , page

14. Attach the guard to the inlet air pipe with the four 1/2" long screws provided.
7. Determine length and install the double-wall terminal vent pipe.
a) Determine length of pipe.
The length of the vent pipe is determined by the installation

within the maximum and minimum requirements. The vent pipe extending through the box

and the inlet air pipe must be one piece of double-wall vent pipe without joints. See FIGURE

13, to determine lengths of each segment and calculate the total length required. The transi-

tion to the single-wall or Category III vent pipe run, must be made a maximum of 6” (152mm)

from the heater side of the box.
b) Install double-wall terminal vent pipe. Being sure the vent pipe is in the proper flow

direction, slide the end through the box. Position the vent pipe so that it will extend between

16" (406mm) and 24” (610mm) past the end of the combustion air pipe and no more than 6”

(152mm) out of the box toward the heater.
Use a taper-type reducer to attach the 5" double-wall vent pipe to the 6" or 7" single-wall or

Category III vent pipe run. Follow the instructions in FIGURE 9 , page 9.
8. Attach the exhaust (vent) cap to the end of the vent pipe. Align the cap so that its baffle

strips are positioned on the horizontal and vertical centerlines (See FIGURE 13). Follow

the instructions in FIGURE 8 , page 9, to attach the exhaust cap. (NOTE: If vent pipe is

inserted from outside, cap may be attached before the double-wall vent pipe is installed. If

cap is attached first, be sure the baffle strips are positioned correctly when attaching the

vent terminal pipe to the vent run.)
9. Seal the vent pipe. Verify that the double-wall section of vent pipe has a slight downward

drop (1/4” per foot/6mm per 305mm) toward the vent terminal end. Use silicone sealant and

seal the circumference of the pipe and the opening of the box. Seal the area around the pipe

FIGURE 12 - Brackets for

Attaching the Concentric

Adapter Box to the Wall