beautypg.com

Vertical vent instructions (cont’d) – Reznor SCE Unit Installation Manual User Manual

Page 16

background image

Form RZ-NA I-SCE, Page 16

VERTICAL VENT

INSTRUCTIONS (cont’d)

Outside view with concentric

adapter box attached to under-

side of roof. Install field-supplied

flashing at roof opening.

Snow Clearance

18” (457mm) minimum

(NOTE: Maximum

from concentric adapter

box is 48” (1219mm)

FIGURE 16 - Slide attached

Combustion Air Pipe up

through the Roof

5. Attach the concentric adapter box to the roof. On the inside, insert the combustion air

pipe up through the opening and attach brackets to the roof. (See FIGURES 15 and 16.)

On the outside, flash the combustion air pipe to the roof. Flashing is field supplied.
6. Determine the length and install the double-wall vent pipe.

a) Determine the length. See FIGURE 15 to determine the required length of the vent pipe.

The vent pipe extending through the box and the inlet air pipe must be one piece of double-

wall vent pipe without joints.
Determine the length by adding the requirements. Starting at the top, the vent pipe must

extend a minimum of 22” (559mm) beyond the top of the inlet air pipe; plus the width of the

roof; plus length of brackets; plus 6” (152mm) through the box; plus 6” (152mm) extending

out of the box on the heater side.
b) Install the pipe. Being sure the pipe is in the proper flow direction, slide the end into the

box and out through the combustion air pipe. Position the vent pipe to the lengths deter-

mined above. NOTE: The double-wall vent pipe does not attach to the box. The installer

must provide support.
Follow the instructions in FIGURE 9 , page 9, for connecting the double-wall pipe to the

single-wall pipe or Category III vent pipe run. A taper-type reducer is required.
Seal the circumference of the pipe and the opening of the box with silicone sealant. Seal the

area around the pipe completely.

FIGURE 15 - Assemble

Concentric Adapter Box,

Outdoor Combustion Air

Pipe, and Double-Wall Vent

Pipe

b). Attach the outside portion of the combustion air pipe to the box. Determine the length of

the combustion air pipe so that dimension ”X” in FIGURE 15 is equal to the bracket length,

plus the roof thickness, plus anticipated snow depth, but does not exceed 48“ (1219mm) or

have less than 18” (457mm) of pipe above the roof. Attach the inlet air pipe to the collar of the

concentric adapter box with sheetmetal screws.

Concentric

Adapter Box

Mounting Brackets

X = length of

combustion air pipe required

through and above the roof.

Height from box to top of inlet air

pipe must not exceed 48” (1219mm).

Minimum height above the roof is

18” (457mm) and must be higher

than anticipated snow depth.

First, attach Combustion Air Pipe and install the

Concentric Box

1) Determine length (X) of pipe (see requirements

on the left).

2) Attach the pipe to the collar on the box.

3) Attach the brackets to the roof.

Vent Flow

22” (559mm) minimum

Cold Climate NOTE:

In geographic areas where

the design ambient is -10°F

or lower, this minimum

height is 34” (864mm).

Collar for Indoor Portion of

the Combustion Air Pipe

Double-Wall Vent Pipe -

Extend length of double-wall

vent pipe a maximum of 6”

(152mm) below the box.

After box is installed, install Concentric Vent Pipe -

One piece of continuous double-wall pipe must extend

from a minimum of 3” (76mm) above the outer com-

bustion air pipe to a maximum of 6” (152mm) below

the box. (NOTE: Vent pipe does not attach to the box;

it must be supported.)

1) Calculate height (see requirements on the left).

2) Be sure vent flow marking on pipe is in the right

direction.

3) Slide pipe through the box and the outer inlet air pipe.

4) Attach to vent run no more than 6” (152mm) from the

adapter box. See instructions on page 9.

Vent pipe

extending

through the

box and the

combustion

air pipe MUST

be one continuous

piece of double-

wall vent pipe.

A second section

of double-wall pipe

is permitted, joining

the long continuous

piece of vent pipe a

minimum of 3” (76mm)

above the top of the

combustion air pipe.

3” (76mm)

minimum