6) Clearance

Do not enclose the vent pipe or place pipe closer than 6" (152mm) to combustible material.

All separated combustion installations require a concentric adapter box as illustrated in FIGURE 10.

The concentric adapter box is included in the vent/combustion air kit. Installation instructions depend

on whether the vent system is horizontal (Option CC6) or vertical (Option CC2).

7) Concentric

Adapter Box

FIGURE 10 - A Concentric Adapter Box is a

Required Part of all Model SCE Installations

View of Heater Connection Side

View of Vent Terminal Connection Side

End View

showing

Airflow

Gray Arrows

show Flow of

Combustion Air

Vent (exhaust gas) flows through

field-supplied double-wall pipe

that extends straight through

the concentric adapter box.

P/N 205885, Concentric Adapter Box

Top View

Heater Side View

6” Collar for

Combustion

Air Pipe

Opening for

vent pipe to

pass through

the box

2” (51mm)

2” (51mm)

6-1/32”

(153mm)

8” dia Collar for

Combustion Air Pipe

14-1/4”

(362mm)

(127mm)

5-7/32”

(133mm)

5-21/32”

(144mm)

diameter

5-9/32”

(134mm)

(102mm)

13-3/8” (340mm)

Collar for connecting

indoor portion of the

combustion air pipe

Opening for

double-wall vent

pipe to pass

through the box.

Collar for

attaching outside

concentric portion

of the combustion

air pipe

9. Venting and Combustion Air (cont'd)

Specific Venting Requirements (cont'd)

Concentric Adapter Box Airflow