beautypg.com

Operating valve – Reznor SCE Unit Installation Manual User Manual

Page 25

background image

Form RZ-NA I-SCE, Mfg #207697 Rev 7,

Page 25

18. Operating

Valve

All furnaces are equipped with a 24-volt combination valve which includes the automatic electric

on-off valve controlled by the room thermostat, the pressure regulator, the safety pilot valve, and

the manual shutoff valve. The standard gas valve allows for single-stage control from a single-

stage, 24-volt thermostat.

WARNING: The operating valve is the prime safety shutoff. All gas supply

lines must be free of dirt or scale before connecting the unit to ensure positive
closure. See Hazard Levels, page 2.

19. Optional 2-

Stage

Operation -

Heating Only

Application

The standard combination control valve is replaced with a two-stage combination gas control

valve providing for low fire or high fire operation controlled by a two-stage thermostat. First stage

(low fire) is factory set (not field adjustable). Both high and low stages are controlled by a Servo

regulator, maintaining constant gas input under wide variations in gas supply pressure. See

instructions packed with the unit for specific gas valve specifications, wiring, and operating

instructions.

20. Optional 2-

Stage

Operation -

Makeup Air

Application

Two-stage makeup air units are equipped with a two-stage gas valve, but instead of control from

a two-stage room thermostat, the outlet air temperature is monitored and controlled by a two-

stage ductstat. When the discharge air temperature drops to the setpoint, low fire is energized. If

low fire cannot satisfy the ductstat setting, high fire is energized.
Makeup air applications are usually adjusted to discharge an outlet air temperature between 65°F

and 75°F. In all applications, the allowable temperature rise of the furnace in the installation

dictates the limits of the ductstat temperature setting.
Depending on the option selection, the factory-installed sensor is either field-connected by

capillary tubing to the unit-mounted ductstat (FIGURE 24) or electrically connected to a remote

electronic temperature selector ( FIGURE 25). The remote temperature selector is available with or

without a display module.
See FIGURE 23 for a general location of the factory-installed sensor with either the factory-

mounted or the remote ductstat selector option.

Optional Ductstat with Capillary Tubing (Option AG3)

-- The control illustrated in FIGURE 24

has an adjustable range from 0° to 100°F with a fixed differential of 2-1/2°F. Due to different CFM

settings and outside air temperatures, the average downstream outlet temperature may not match

the ductstat setting exactly. After the installation is complete, adjust the setpoint of the ductstat

to achieve the desired average outlet air temperature.
Optional Ductstat with Electronic Remote Setpoint Module (Options AG15 and AG16) --

The

field-installed sensing probe is field-wired to a remote temperature selector with a temperature

operating range to 130°F. The remote modules and sensing probe are shipped separately for field

installation. Follow the wiring diagram with the unit and the manufacturer's instructions for wiring

and installation. CAUTION: Be sure heat/cool selector switch is set at "Heat" position. There will

be one module for selecting temperature and one-stage adder module. The digital display module

is optional. See FIGURE 25 .

FIGURE 23 - Duct

Temperature Sensor

Location

FIGURE 24 - Ductstat

Control in Options AG3

Factory

set at

70°F

1. Remove access panel in ductwork

adjacent to control compartment

access panel.

2. Element is retained by spring clips.
3. Round gasket and metal retaining

plate provide airtight seal for capillary

and must be removed to remove the

element.