beautypg.com

2 clearances, 0 positioning and mounting 6.0 mechanical, 1 gas piping and pressures – Reznor CAUA Unit Installation Manual User Manual

Page 6: 0 clearances and dimensions (cont'd), 0 positioning and mounting, 0 mechanical

background image

Form I-CAUA, P/N 164771 R8, Page 6

Vibration Isolation

Pads, Option PC4

4.0 Clearances

and

Dimensions

(cont'd)

Determine the position of the heater with regard to clearances, venting, combustion air,

gas supply connection, electrical supply connection, and the inlet air opening. The inlet

air opening may be in the right side, in the left side, in the rear, or in the bottom of the

cabinet (See

FIGURE 1) and must be cut by the installer.

CAUTION: Use tin snips or aviation shears to cut the inlet air

opening. Use caution as the cut edges of the metal will be

sharp.

Either cut out the inlet air opening now or when attaching the ductwork, filter cabinet,

or mixing box. If the application includes an optional bottom filter cabinet, either lay the

heater down (note weight in

TABLE 1) and cut the opening now or cut it out from the

inside after the heater is placed on the bottom filter cabinet.

NOTE: If ordered with an

optional inlet base, the heater is shipped with a factory provided opening in the bottom.

5.0 Positioning

and Mounting

If the installation includes optional vibration isolation pads, tip the corner of the unit

enough to slide a pad underneath. Remove the access panel and secure the pad to the

cabinet with the screw provided. Repeat the procedure at all four corners.

PRESSURE TESTING SUPPLY PIPING

Test Pressures Above 1/2 PSI: Disconnect the heater and manual valve

from the gas supply line which is to be tested. Cap or plug the supply line.

Test Pressures Below 1/2 PSI: Before testing, close the manual valve on

the heater.

All piping must be in accordance with requirements outlined in the National Fuel Gas

Code ANSI Z223.1a (latest edition) or CAN/CSA-B149.1 and B149.2 (See Paragraph

1). Gas supply piping installation should conform with good practice and with local

codes.

Unit heaters are orificed for operation with natural gas having a heating value of 1000

(± 50) BTU per cubic ft or propane gas with a heating value of 2550 BTU per cubic ft.

If the gas at the installation site does not meet these specifications, consult the factory

for proper orificing.

6.1 Gas Piping and

Pressures

6.0 Mechanical

TABLE 2 - Required

Clearances

Clearances

inches

mm

Right Side

0

0

Left Side

0

0

Front

36

914

Rear

0

0

Bottom

0

0

Flue Connector

6

152

Top

1

25

4.2 Clearances

The unit must be installed so that the clearances in

TABLE 2 are provided for service

and inspection and for proper spacing from combustible construction. Clearance to

combustibles is defined as the minimum distance from the heater to a surface or object

that is necessary to ensure that a surface temperature of 90°F above the surrounding

ambient temperature is not exceeded.

WARNING:

This appliance is equipped for a maximum gas supply

pressure of 1/2 psi, 3.5 kPa, or 14 inches water column.

Supply pressure higher than 1/2 psi requires installation of

an additional lockup-type service regulator external to the

unit.