beautypg.com

8 flue wrapper condensate drain, 0 electrical and wiring, 1 wiring – Reznor CAUA Unit Installation Manual User Manual

Page 34: 0 mechanical (cont'd), 7 burner condensate drain (cont'd)

background image

Form I-CAUA, P/N 164771 R8, Page 34

3

4

2

1

a) Assemble the brass nut, the sealing washer, and

the 90° fitting.

b) Position the threaded fitting up through the hole

so that the hose barb is toward the bushing in the

side of the cabinet. Attach using the silver-colored

locknut.

c) Under the burner, push the tubing onto the hose

barb, being sure that it is secure. Maintaining a

downward slope, extend the hose out through the

cabinet side.

d) Just after exiting the cabinet,

create a trap in the

line by making a loop in the hose. Secure the

loop with the wire ties.

e) Continue downward with the tubing, connecting it

into the coil drain pipe.

FIGURE 27 - Burner Condensate Drain

Connection

Hex Locknut (silver)

Burner Bottom Pan

Sealing Washer

Brass Nut

90° Nylon Fitting

6.0 Mechanical

(cont'd)

6.8 Flue Wrapper

Condensate

Drain

If equipped with a makeup air option to allow inlet air less than 35°F (Option AD4), the

flue wrapper will have a condensate drain. Follow the instructions in

FIGURE 28. Peri-

odic cleaning of the condensate drain is required.

FIGURE 28 - Unit with

Option AD4 which

includes a Condensate

Drain on the Flue

Wrapper

Condensate Drain

Tubing from Flue

Wrapper

Tubing exits through an

opening in side panel.

Connect it into either

the burner or coil

drain or directly

into a sanitary drain.

Periodic cleaning of

the condensate drain

is required.

Flue

Wrapper

6.7 Burner Condensate Drain (cont'd)

7.0 Electrical and

Wiring

All electrical wiring and connections, including electrical grounding, MUST be made

in accordance with the National Electric Code ANSI/NFPA No. 70 (latest edition) or,

in Canada, the Canadian Electrical Code, Part I-C.S.A. Standard C22.1. In addition,

the installer should be aware of and comply with any local ordinances or gas company

requirements.

7.1 Wiring

Check the rating plate on the heater for the supply voltage and current requirements.

A separate line voltage supply with fused disconnect switch should be run directly from

the main electrical panel to the heater. All external wiring must be within approved con-

duit and have a minimum temperature rise rating of 60°C. Conduit from the disconnect

switch must be run so as not to interfere with the service panels of the heater.
Use an amp meter to check motor amps.

TABLE 26 lists full load amps for all HP's

and voltages. Amps may be adjusted downward by reducing blower RPM or increasing

duct system static pressure.

WARNING

If you turn off the

power supply, turn off

the gas. See Hazard

Levels, page 2.

Motor Amps

4. Locate the hole in the bottom center of the burner pan and remove the plug.

Follow the instructions in

FIGURE 27 to install the drain. Complete all steps

as listed in the illustration. When installation of the burner condensate drain is

complete, re-assemble the heater.

Instructions for Installing Burner Condensate Drain (cont'd)