beautypg.com

0 mechanical (cont'd), 2 venting and combustion air (cont'd) – Reznor CAUA Unit Installation Manual User Manual

Page 16

background image

Form I-CAUA, P/N 164771 R8, Page 16

6-15/16” (176mm)

Concentric Adapter Box

Double-Wall

Vent Pipe -

Pitch to

Drain

Thimble

Combustion Air Pipe - Pitch to Drain

3 ft (1M)

minimum

3 ft (1M)

minimum

6 ft (1.8M) minimum

Adjoining Building

Building Projection

Building Overhang

W a l l

Inlet Air

Guard

Exhaust (Vent) Cap

IMPORTANT: Install exhaust cap so the baffles

are positioned at 12:00, 3:00, 6:00, and 9:00 o’clock.

Side View

16” (406mm)

minimum

24” (610mm)

maximum

Concentric

Adapter

Box

Wall

Screened

Exhaust

Cap

Inlet Air

Guard

Combustion Air to heater (seal joints)

Vent (Flue Exhaust) Pipe

from heater (seal joints)

Heater

Distance between the

Concentric Adapter Box

and the Heater

For Maximum Length,

see Table on page 10.

Minimum length is 5 ft (1.5M).

Attach double-vent pipe to vent run no

more than 6” (152mm) from the box. A

taper-type reducer is required on Sizes

150, 200, 300, 350, and 400.

2” (51mm) if wall is combustible

Attach box to wall with brackets.

One piece of

Double-Wall

Vent Pipe

2” (51mm)

(152

mm)

1” (25mm)

minimum

48”

(1219mm)

maximum

Top View

FIGURE 8 - Installation

of a Typical Separated-

Combustion Unit with

Horizontal Vent and

Combustion Air Pipes

(Option CC6)

9) Seal the vent pipe. Verify that the double-wall section of vent pipe has a slight

downward drop (1/4" per foot/6mm per 305mm) toward the vent terminal end. Use

silicone sealant and seal the circumference of the pipe and the opening of the box.

Seal the area around the pipe completely.
10) Attach the indoor combustion air pipe. On Sizes 150 and 200, install a taper-

type enlarger as illustrated in

FIGURE 4A, page 11. On Sizes 250, 300, 350, and

400, attach the single-wall combustion air pipe run to the collar on the concentric

adapter box with sheetmetal screws. Seal joints with tape or sealant.
Installation of the horizontal vent and combustion air system on your separated com-

bustion unit is complete. Verify compliance with all venting installation requirements,

pages 9-13, and

FIGURE 8.

6.0 Mechanical

(cont'd)

6.2 Venting and

Combustion Air

(cont'd)

6.2.1 Venting and Combustion Air Requirements for a Separated

Combustion (cont'd)

6.2.1.1 HORIZONTAL Vent Instructions (cont'd)