beautypg.com

0 mechanical (cont'd), 2 venting and combustion air (cont'd) – Reznor CAUA Unit Installation Manual User Manual

Page 20

background image

Form I-CAUA, P/N 164771 R8, Page 20

6.2.2 Venting and Combustion Air Requirements for Power Vent

Drawing Combustion Air from THE INSIDE SPACE and Venting

Flue Products to the Outdoors

If the environment has a positive pressure and is such that it is not detrimental to com-

bustion air, the power venting system in this section may be installed.

To provide combustion air to the heater, sufficient air must enter the equipment location

to replace that exhausted through the heater vent system. In the past, the infiltration of

outside air assumed in heat loss calculations (one air change per hour) was assumed

to be sufficient. However, current construction methods using more insulation, vapor

barriers, tighter fitting and gasketed doors and windows, weather-stripping, and/or

mechanical exhaust fans may now require the introduction of outside air through wall

openings or ductwork to the equipment room.

The requirements for combustion and ventilation air depend upon whether the unit

is located in a confined or unconfined space. An "unconfined space" is defined as a

space whose volume is not less than 50 cubic feet per 1000 BTUH of the installed

appliance.

Under all conditions, enough air must be provided to ensure there will

not be a negative pressure condition within the equipment room or space. Follow the

specific requirements below for a confined space installation.

Confined Space Installation - Do not install a unit in a confined space without provid-

ing wall openings leading to and from the space. Provide openings near the floor and

ceiling for ventilation and air for combustion as shown in

FIGURE 14, depending on the

combustion air source as noted in Items 1, 2, and 3 below.

Venter Outlet

Attachment

Requirements

2) Venter (Flue) Outlet

TABLE 12 - Venter

Model Sizes

Venter Outlet Diameter

150, 200, 250

5 inches

127 mm

300, 350, 400

6 inches

152 mm

• A minimum of 12" of straight pipe is required at the venter outlet before installing

an elbow in the vent system. An elbow should never be attached directly to the

venter. An elbow attached to the straight pipe can be in any position at or above

horizontal. See

FIGURE 15.

• Do not install dampers or any other type of flue restrictor device.

All pipe is field supplied. Use either vent pipe approved for a Category III appliance or

single-wall, 26-gauge or heavier galvanized (or a material of equivalent durability and

corrosion resistance) vent pipe.
If local code requires, a double-wall terminal section may be installed with a single-wall

or Category III vent pipe run.
Or, if at least 1/2 of the equivalent vent length is vertical, vent pipe approved for a

Category I heater may be used. Single-wall pipe or double-wall (Type B) vent pipe are

suitable for use with a Category I heater.

Power Venting

Requirements

1) Type of Pipe

Outlet Size

FIGURE 14 - Confined Space:

A space whose volume is less

than 50 cubic feet per 1000

BTUH of the installed appliance

input rating

Confined

Space

(3)

(3)

(1)

(1)

(2)

(2)

Add total BTUH of all appliances in the confined space and divide by figures below for

square inch free area size of each (top and bottom) opening.

1. Air from inside the building -- openings 1 square inch free area per 1000 BTUH.

Never less than 100 square inches free area for each opening.

See (1) in FIGURE 14.

2. Air from outside through duct -- openings 1 square inch free area per 2000 BTUH.

See (2) in FIGURE 14.

3. Air direct from outside -- openings 1 square inch free area per 4000 BTUH. See

(3) in FIGURE 14.

NOTE: For further details on

supplying combustion air to

a confined space, see the

National Fuel Gas Code ANSI

Z223.1a (latest edition).

6.0 Mechanical

(cont'd)

6.2 Venting and

Combustion Air

(cont'd)