beautypg.com

0 mechanical (cont'd), 2 venting and combustion air (cont'd) – Reznor CAUA Unit Installation Manual User Manual

Page 14

background image

Form I-CAUA, P/N 164771 R8, Page 14

6.2.1.1 HORIZONTAL

Vent Instructions
Components

Required - Factory

and Field

TABLE 9 - Parts in

Option CC6, Horizontal

Vent Terminal/

Combustion Air

Package

Field-supplied

installation

requirements:

• Vent pipes - see requirements, page 9.

• Combustion air pipes - see requirements, page 9.

• Taper-type vent pipe diameter reducers and/or increasers as required.

• Thimble (a thimble is not required if wall is of non-combustible construction).

• Flashing.

• Sheetmetal screws, tape, and sealant as required.

Installation Instructions

for Horizontal Vent Kit,

Option CC6

1) Determine the location on the outside wall for the vent terminal. Location

must comply with vent length requirements, Requirement No. 3 on page 10. Allow

1/4" per foot (6mm per 305mm) downward pitch for condensate drain.
The distance of the termination of the horizontal vent from adjacent public walkways,

adjacent buildings, openable windows, and building openings must be in accordance

with local codes or, in the absence of local codes, must conform with National Fuel

Gas Code Z223.2. Local codes supersede all provisions in these instructions and in

the National Fuel Gas Code. Minimum clearances for the horizontal vent terminal are

shown below. Also, select a location that complies with adjoining building clearances

as shown in

FIGURE 8, page 16.

Products of combustion can cause discoloring of some building finishes and

deterioration of masonry materials. Applying a clear silicone sealant that is normally

used to protect concrete driveways can protect masonry materials. If discoloration is

an esthetic problem re-locate the vent or install a vertical vent.

WARNING: All vent

terminals must

be positioned or

located away from

fresh air intakes,

doors and windows

to preclude

combustion

products from

entering occupied

space. Failure

to comply could

result in severe

personal injury

or death and/or

property damage.

TABLE 10 - Clearances

to Horizontal Vent

Terminal

Screened

Exhaust

Assembly

Inlet

Guard

Qty

150,

200

250, 300,

350, 400

Description

1 205882 205883 Complete Horizontal Vent Kit (Same as

Option CC6)

1

205884 205885 Concentric Adapter Box Assembly (FIGURE

5, page 12.)

1

155096

53316 Screened Exhaust Assembly (illustrated

below)

1

205893 205894 Inlet Guard (illustrated below)

4

37661

37661 #10-16 x 1/2" long Screws to attach the

inlet guard

2

207232 207232 Brackets for attaching Concentric Adapter

Box (

FIGURE 7, page 15.)

1

53335

53335 Tube of High Temperature Silicone Sealant

Structure

Minimum Clearances for Vent Terminal Location

(all directions unless specified)

Forced air inlet within 10 ft (3.1M)*

3 ft (0.9M) above

Combustion air inlet of another appliance 6 ft (1.8M)

Door, window, or gravity air inlet (any

building opening)

4 ft (1.2M) horizontally

4 ft (1.2M) below

1 ft (305mm) above

Electric meter, gas meter ** and relief

equipment

U.S. - 4 ft (1.2M) horizontally;

Canada - 6 ft (1.8M)

Gas regulator **

U.S. - 3 ft (0.9M); Canada - 6 ft (1.8M) horizontally

Adjoining building or parapet

6 ft (1.8M)

Adjacent public walkways

7 ft (2.1M) above

Grade (ground level)

3 ft (.9M) above***

*Does not apply to the inlet of a direct vent appliance. **Do not terminate the vent directly

above a gas meter or service regulator. *** Consider local snow depth conditions. The vent

must be at least 6” (152mm) higher than anticipated snow depth.

2) Install the Vent Pipe and Combustion Air Pipe Runs - Use the type of pipe

specified in Requirement No. 1, page 9. Comply with requirements in Requirement

No. 2 and No. 4 when attaching pipes to the heater.

6.0 Mechanical

(cont'd)

6.2 Venting and Combustion Air (cont'd)

6.2.1 Venting and Combustion Air Requirements for a Separated

Combustion (cont'd)