beautypg.com

Mechanical (cont'd) – Reznor CAUA Unit Installation Manual User Manual

Page 22

background image

Form I-CAUA, P/N 164771 R8, Page 22

Use non-combustible supports on vent pipe. Support horizontal runs every six feet

(1.8M). Support vertical runs of Type "B" double-wall or Category III vent pipe in accor-

dance with the requirements of the pipe manufacturer. Support vertical single-wall pipe

in accordance with accepted industry practices. Do not rely on the heater for support

of either horizontal or vertical vent pipe.

5) Vent System

Support

FIGURE 16B - Attaching

Double-Wall (Type

B) Terminal Pipe to a

Single Wall or Category

III Vent Pipe Run

Figure 16B - STEP 1

On the single-wall pipe or Category

III pipe, place a continual 1/4 inch

bead of silicone sealant around the

circumference.

Figure 16B - STEP 2
Insert the pipe with the sealant into

the inner pipe of the double-wall pipe

until the bead of sealant contacts the

inner pipe creating a sealed joint.

Figure 16B - STEP 3

Spaced equally around the double-

wall pipe, drill three small holes below

the sealant ring. Insert 3/4 inch long

sheetmetal screws to secure the joint. Do

not over tighten screws.

FIGURE 16C - Attaching

Double-Wall (Type B)

Pipe to a Vent Cap

Figure 16C - STEP 1
Place a continual 3/8” bead of silicone

sealant around the circumference of the

vent cap collar. This will prevent any water

inside the vent cap from running down the

double-wall pipe.

Figure 16C - STEP 2

Secure the vent cap to

the double wall pipe by

drilling and inserting a

3/4” long sheetmetal

screw into the vent

cap collar. Do not over

tighten screw.

Insert the collar on the vent cap

inside the inner wall of the double-wall pipe.

Insert as far as possible. Add additional sili-

cone sealant to fully close any gaps between

the vent cap and the double-wall pipe. This is

necessary to prevent water from entering the

double-wall pipe.

Figure 16C - STEP 3

Vent

Pipe

with

Sealant

from

STEP 1

Double-

Wall Pipe

Do STEP 2

immediately

following

STEP 1.

4) Joints and Sealing (cont'd)

Single-Wall

or Category

III Vent Pipe

Do STEP 2

immediately

after STEP 1.

6) Condensation

Any length of single-wall vent pipe exposed to cold air or run through an unheated

area or an area with an ambient temperature of 45°F or less must be insulated along

its entire length with a minimum of 1/2" foil-faced fiberglass, 1-1/2# density insulation.

Where extreme conditions are anticipated, install a means of condensate disposal.

6. Mechanical

(cont'd)

6.2 Venting and

Combustion Air

(cont'd)

6.2.2 Venting and

Combustion Air

Requirements for

Power Vent (cont'd)

7) Vent Terminal (Pipe

and Vent Cap)

The vent system must be terminated with the type of vent cap approved for use with

this heater. The vent cap must be the same size as the vent pipe. Use of the vent cap