beautypg.com

Reznor CAUA Unit Installation Manual User Manual

Page 19

background image

Form I-CAUA, P/N 164771 R8, Page 19

SECOND, Install the Exhaust (Vent) Terminal.

Follow the instructions in FIGURE 4A, page 11.

FIRST, Install Combustion Air Inlet.

1) Slide the combustion air inlet over the vent pipe.

2) Fasten bottom of inlet to the combustion air pipe

with sheetmetal screws. Be sure not to penetrate

the vent pipe.

3) At the top, completely seal the space between the

vent pipe and the air inlet with silicone.

Double-wall V

ent Pipe

Cold Climate NOTE: In geographic areas

where the design ambient is -10°F or lower,

this minimum height is 24” (610 mm)

Single-wall Combustion Air Pipe

FIGURE 12 -

Install Combustion Air Inlet and Vent Terminal

the end is no more than 6" (152mm) below the

box. The upper end should extend at least 3"

(76mm) above the combustion air pipe.

NOTE:

The double-wall vent pipe does not attach to the

box.

The installer must provide support.

Follow the instructions in

FIGURE 4B, page 11,

for connecting the double-wall pipe to the single-

wall pipe or Category III vent pipe run. For CAUA

Sizes 150, 200, 300, 350, and 400, a taper-type

reducer is required.
Seal the circumference of the pipe and the open-

ing of the box with silicone sealant. Seal the area

around the pipe completely.
7) On the outside, slide the combustion air

inlet over the vent pipe and fasten the collar to

the combustion air pipe with sheetmetal screws.

See

FIGURE 12. Seal the opening at the top

between the vent pipe and the combustion

air inlet with silicone sealant to prevent water

leakage.

8) Attach the exhaust (vent) cap. Follow the illustrated

instructions in

FIGURE 4A, page 11.

FIGURE 13 - Installation of Unit with

Vertical Vent Terminal/Combustion Air

Inlet (Option CC2)

Rear

View

Side View

9) Attach the indoor combustion air pipe. Use sheetmetal

screws to attach the single-wall combustion air pipe run to the

collar on the concentric adapter box. On Sizes 150 and 200,

install a taper type enlarger as illustrated in

FIGURE 6A, page

13.
Seal joint with tape or sealant.
Installation of the vertical vent and combustion air system on

your separated-combustion unit is complete.

Verify compliance

with all venting installation requirements, pages 9-13, and

FIGURE 13.