beautypg.com

Reznor CAUA Unit Installation Manual User Manual

Page 17

background image

Form I-CAUA, P/N 164771 R8, Page 17

TABLE 11 - Parts in

Option CC2, Vertical

Vent Terminal/

Combustion Air

Package

Components Required - Factory and Field

6.2.1.2 VERTICAL

Vent Instructions

Field-supplied

installation

requirements:

• Vent pipes - see requirements, page 9.

• Combustion air pipes - see requirements, page 9.

• Taper-type pipe diameter reducers and/or increasers as required.

• Thimble (a thimble is not required if wall is of non-combustible construction).

• Flashing.

• Sheetmetal screws, tape, and sealant as required.

Installation Instructions

for Vertical Vent/

Combustion Air Kit

Option CC2

1) Determine the location of the vent terminal.

Select a location away from fresh air intakes, allowing space for the concentric

adapter box inside. Vent terminal must be located from adjacent buildings as shown

in

FIGURE 13, page 19.

Exhaust

(Vent)

Terminal

Combustion

Air Inlet

Qty

150,

200

250, 300,

350, 400

Description

1 205895 205896 Complete Vertical Vent Kit (Same

as Option CC2)

1 205884 205885 Concentric Adapter Box Assembly

(See

FIGURE 5, page 12)

1 110051 110052 Exhaust (Vent) Terminal
1 155635 53330 Combustion Air

2 207232 207232 Brackets for attaching Concentric

Adapter Box (See

FIGURE 9, pg 19)

1

53335

53335 Tube of High Temperature Silicone

Sealant

4) Prepare the Concentric

Adapter Box

a. Attach the brackets to

the box. Follow the instruc-

tions in

FIGURE 9.

FIGURE 9 - Brackets

for Attaching the

Concentric Adapter Box

to the Roof

1) Attach the Brackets to the Box - The 6”

(152mm) portion of each bracket is designed

with five 7/32” diameter holes so that attach-

ment to the box can be adjusted.

If the roof is combustible, position brackets to allow

for a 2” (51mm) clearance between the box and the

roof. After careful positioning, use sheetmetal screws

to attach the brackets. NOTE: If any holes are made

in the box in error, they must be sealed.

2) Attach the Box to the Roof (Step 5)

When the box is attached to the roof in Step 5, use the

2-1/2” (64mm) portion of the brackets. To adjust to

construction each bracket has three 7/32” diameter holes.

WARNING

All vent terminals must be positioned or located away from fresh air intakes, doors, and windows

to preclude combustion products from entering occupied space. Failure to comply could result in

severe personal injury or death and/or property damage.

2) Install the Vent Pipe and Combustion Air Pipe Run - Use the type of pipe

specified (Requirement No. 1, page 9), and comply with the attachment requirements

in Requirement No. 2, page 9. Length must comply with Requirement No. 3, page 10.
Seal all joints. Due to the high temperature,

do not enclose the exhaust pipe or place

pipe closer than 6" (152 mm) to combustible material. Provide supports for the pipes.

Extend the runs to close to the roof at the location selected in No. 1 for the vent

terminal.
3) Prepare a hole [6" (152mm) diameter for CAUA Sizes 150 and 200 or 8"

(203mm) diameter for Sizes 250, 300, 350, and 400] through the roof for the

combustion air pipe. A thimble may or may not be required depending on building

construction and/or local codes. The combustion air pipe serves as clearance for the

vent pipe on non-combustible construction.