beautypg.com

Reznor CAUA Unit Installation Manual User Manual

Page 11

background image

Form I-CAUA, P/N 164771 R8, Page 11

6) Support

Support horizontal runs every six feet (1.8M). Support vertical runs of Category III vent

pipe in accordance with the requirements of the pipe manufacturer.
Support vertical single-wall pipe in accordance with accepted industry practices.
Do not rely on the heater or the adapter box for support of either horizontal or vertical

pipes. Use non-combustible supports on vent pipe.

FIGURE 4A - Follow

STEPS to join Double-

Wall (Type B) Pipe and

the Vent Terminal Cap

(horizontal or vertical)

Figure 4A - STEP 1

Place a continual 3/8” bead of silicone sealant

around the circumference of the vent cap collar.

This will prevent any water inside the vent cap

from running down the double-wall pipe.
Do STEP 2 immediately following STEP 1.

Figure 4A - STEP 2

Insert the collar on the vent cap inside

the inner wall of the double-wall pipe.

Insert as far as possible. Add additional

silicone sealant to fully close any gaps

between the vent cap and the double

wall pipe. This is necessary to prevent

water from entering the double wall

pipe.

Secure the vent cap to the double-wall pipe by drilling and inserting a 3/4” long

sheetmetal screw into the vent cap collar. Do not overtighten screw.

Figure 4A - STEP 3

(NOTE: Pipes and vent

caps may not look exactly

as shown in the illustra-

tions. Instructions apply to

both horizontal and vertical

vent kits.)

FIGURE 4B - Follow

STEPS when joining

the Double-Wall (Type

B) Pipe to the Single-

Wall or Category III

Vent Run

Figure 4B - STEP 1

On the single-wall or Category III

vent pipe or the taper-type reducer,

place a continual 1/4” bead of sili-

cone sealant around the circumfer-

ence.

Figure 4B - STEP 2

Insert the pipe with the bead of sealant

into the inner pipe of the double-wall

pipe until the bead of sealant contacts

the inner pipe creating a sealed joint.

Figure 4B - STEP 3

Make this connection a maximum of 6" (152mm) from the concentric adapter box.

Double-

Wall Pipe

Single-wall

or Category

III vent pipe

or taper-type

reducer

Spaced equally around the double-

wall pipe, drill three small holes

below the sealant ring. Insert 3/4

inch long sheetmetal screws to

secure the joint.

Do not overtighten screws.

Do STEP 2

immediately

following

STEP 1.

NOTE: The double-wall

vent terminal pipe does not

attach to the concentric

adapter box and must be

supported during installa-

tion.

7) Clearance

Do not enclose the vent pipe or place pipe closer than 6" (152mm) to combustible

material.