Ft-10, Rofibus, Only – Flintec FT-10xx User Manual
Page 53: ] profibus

FT-10 Smart Process Indicator, Technical Manual, Rev. 1.0, January 2014
9. P
ROFIBUS
(
ONLY
FT-10
PB
)
In Profibus DPV1 interface, baud rate is detected automatically. Supported baud rates are 9.6 kbps, 19.2
kbps, 45.45 kbps, 93.75 kbps, 187.5 kbps, 500 kbps, 1.5 Mbps, 3 Mbps, 6 Mbps and 12 Mbps. No ‘baud
rate’ instance exists.
After programming Profibus related parameters of the FT-10 PB indicator, you can communicate with the
instrument. GSD file is available in CD which is supplied together with the instrument.
[05-] Profibus
This sub-block includes the parameters related with the Profibus interfaces of FT-10 indicator.
[050 0 ] Data Format
0 : Signed 32 bit integer, no decimal point implied
1 : 32 bit float, decimal point implied
[051 000] Rack Address
The Profibus rack address of FT-10 will be entered via keypad between 1 to 126.
There are two LED’s near the Profibus connector which are ;
ST Status LED
State
Indication
Comment
Off
Not power or not initialized
No power or profibus module is in
initialization state
Green
Initialized
Flashing Green
Initialized, diagnostic event(s)
present
Diagnostic is active
Red
Exception error
There is an exception error
OP Operation mode LED
State
Indication
Comment
Off
Not online /No power
Check power and cable
Green
On-line, data exchange
-
Flashing Green
On-line, clear
-
Flashing Red
(2 flash)
PROFIBUS configuration error
Check GSD file configuration.
1
OP Operation mode LED
2
ST Status LED
3
Profibus Connector