EVCO EPU2BXP1S1 User Manual
Page 61
EVCO S.p.A.
c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104
EVCO
page 61 of 68
Bit16=AL16
0x0301
770
PackedAlarm_2
0
0
65535
Bit1=AL17,
Bit2=AL18,
Bit3=AL19,
Bit4=AL20,
Bit5=AL21,
Bit6=AL22,
Bit7=AL23, Bit8=Free,
Bit9=AL25,
Bit10=AL26,
Bit11=AL27,
Bit12=AL28,
Bit13=AL29
R/W
0x0400
1025
Status_OnOff_bySUP
0
0
1
R/W
0x0500
1281
CLOCK_RTC ( Low )
-
01/01/2000
19/01/2068
03:14:07
R/W
0x0501
1282
CLOCK_RTC ( High )
0x0502
1283
StatusUnit
0
0
5
R/W
0x0503
1284
UI_MainLabelDown
0
0
8
R/W
0x0504
1285
Status_SupplyFan
0
0
9
0=Disabilitato, 1=OFF,
2=Wait ON, 3=ON,
4=Wait OFF, 5=ALL,
6=Manual
R/W
0x0505
1286
Status_ReturnFan
0
0
9
0=Disabilitato, 1=OFF,
2=Wait ON, 3=ON,
4=Wait OFF, 5=ALL,
6=Manual
R/W
0x0506
1287
UI_byPassAntiFreeze
0
0
1
R/W
0x0507
1288
Status_AirNEUF
0
0
5
R/W
0x0508
1289
byPassRecover_Summer
0
0
1
R/W
0x0509
1290
Status_Resistor1
0
0
5
0=Disabilitato, 1=OFF,
2=Wait ON, 3=ON,
4=Wait OFF, 5=ALL
R/W
0x050A 1291
Status_Resistor2
0
0
5
0=Disabilitato, 1=OFF,
2=Wait ON, 3=ON,
4=Wait OFF, 5=ALL
R/W
0x050B 1292
Status_Resistor3
0
0
5
0=Disabilitato, 1=OFF,
2=Wait ON, 3=ON,
4=Wait OFF, 5=ALL
R/W
0x050C 1293
active_ProbeHeating
0.0
-3276.8
3276.7
R/O
0x050D 1294
active_SetPointHeating
0.0
-20.0
230.0
R/W
0x050E
1295
active_HeatingPower
0.00
0.00
100.00
R/W
0x050F
1296
Status_MixAirShutter
0
0
5
R/W
0x0510
1297
Request_AirQuality
0.00
0.00
100.00
R/W
0x0511
1298
Req_FreeCoolingHeating
0.00
0.00
100.00
R/W
0x0606
1543
SPHR_SetPoint_Return
20.0
-20.0
230.0
R/W
0x0607
1544
SPHM_SetPoint_Supply
22.0
-20.0
230.0
R/W