EVCO EPU2BXP1S1 User Manual
Page 36
EVCO S.p.A.
c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104
EVCO
page 36 of 68
PF22
Speed variator value corresponding to speed V2
66.50
0.00
100.00
%
IS-F
PF23
Speed variator value corresponding to speed V3
100.00
0.00
100.00
%
IS-F
PF30
Minimum speed for modulating fan
0.0
0.0
PF31
%
IS-F
PF31
Maximum speed for modulating fan
100.0
PF30
100.0
%
IS-F
PF32
Static pressure setpoint ramp adjustment
300
0
30000
Pa/min
IS-F
PF33
V1 static pressure setpoint adjustment
300
0
30000
Pa
IS-F
PF34
V2 static pressure setpoint adjustment
400
0
30000
Pa
IS-F
PF35
V3 static pressure setpoint adjustment
500
0
30000
Pa
IS-F
PF36
Setpoint adjustment proportional band
200
0
10000
Pa
IS-F
PF37
Integral time setting static pressure
0
0
300
Sec
IS-F
PF38
Speed controller for pressure switch in
probe error
30.0
0.0
100.0
%
IS-F
HEATING COILS
This menu is only accessible if PG02>0
Pb01
Regulation probe for heating
0: Supply Probe
1: Return Probe
0
0
1
IS-B
FREECOOLING
Pr04
Outside air/recovery heat exchanger by-
pass temperature set point in summer
15.0
PH01
PH02
°C
°F
IS-FC
Pr05
Return air/recovery heat exchanger by-
pass temperature set point in summer
22.0
PH01
PH02
°C
°F
IS-FC
ALARM PARAMETERS
PA01
Enabling fans working hours alarm
Active (1)
Not-
active
(0)
Active (1)
-
IS-S
PA02
Signals working hours alarms on alarm
relay
No (0)
No (0)
Yes (1)
-
IS-S
PA04
Signals the supply/return fans thermal
overload alarm on the alarm relay
Yes (1)
No (0)
Yes (1)
-
IS-S
PA07
Differential pressure switch alarm delay on
unit start-up
60
0
999
sec
IS-S
PA11
Signals the coil anti-freeze alarm on the
alarm relay
Yes (1)
No (0)
Yes (1)
-
IS-S
Only if
PG02=1
PA15
Signalling of the outside air damper limit
switch alarm on alarm relay
Yes (1)
No (0)
Yes (1)
-
IS-S
PA21
Signalling of high/low temperature alarms
on the alarm relay
yes (1)
No (0)
Yes (1)
-
IS-S
PA23
Signalling fire/smoke on alarm relay
Yes (1)
No (0)
Yes (1)
-
IS-S
PA25
Signals RTC alarm on alarm relay
Yes (1)
No (0)
Yes (1)
-
IS-S
PA27
Signals probe alarms on alarm relay
Yes (1)
No (0)
Yes (1)
-
IS-S
VARIOUS PARAMETERS
PH01
Minimum temperature value
-15.0
-20.0
-4.0
PH02
°C
°F
IS-V
PH02
Maximum temperature value
95.0
PH01
110.0
230.0
°C
°F
IS-V
PH03
Minimum CO
2
probe PPM value
0
0
PH04
ppm
IS-V