EVCO S.p.A.

c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104

EVCO

page 36 of 68

PF22

Speed variator value corresponding to speed V2

66.50

0.00

100.00

%

IS-F

PF23

Speed variator value corresponding to speed V3

100.00

0.00

100.00

%

IS-F

PF30

Minimum speed for modulating fan

0.0

0.0

PF31

%

IS-F

PF31

Maximum speed for modulating fan

100.0

PF30

100.0

%

IS-F

PF32

Static pressure setpoint ramp adjustment

300

0

30000

Pa/min

IS-F

PF33

V1 static pressure setpoint adjustment

300

0

30000

Pa

IS-F

PF34

V2 static pressure setpoint adjustment

400

0

30000

Pa

IS-F

PF35

V3 static pressure setpoint adjustment

500

0

30000

Pa

IS-F

PF36

Setpoint adjustment proportional band

200

0

10000

Pa

IS-F

PF37

Integral time setting static pressure

0

0

300

Sec

IS-F

PF38

Speed controller for pressure switch in

probe error

30.0

0.0

100.0

%

IS-F

HEATING COILS

This menu is only accessible if PG02>0

Pb01

Regulation probe for heating

0: Supply Probe

1: Return Probe

0

0

1

IS-B

FREECOOLING

Pr04

Outside air/recovery heat exchanger by-

pass temperature set point in summer

15.0

PH01

PH02

°C

°F

IS-FC

Pr05

Return air/recovery heat exchanger by-

pass temperature set point in summer

22.0

PH01

PH02

°C

°F

IS-FC

ALARM PARAMETERS

PA01

Enabling fans working hours alarm

Active (1)

Not-

active

(0)

Active (1)

-

IS-S

PA02

Signals working hours alarms on alarm

relay

No (0)

No (0)

Yes (1)

-

IS-S

PA04

Signals the supply/return fans thermal

overload alarm on the alarm relay

Yes (1)

No (0)

Yes (1)

-

IS-S

PA07

Differential pressure switch alarm delay on

unit start-up

60

0

999

sec

IS-S

PA11

Signals the coil anti-freeze alarm on the

alarm relay

Yes (1)

No (0)

Yes (1)

-

IS-S

Only if

PG02=1

PA15

Signalling of the outside air damper limit

switch alarm on alarm relay

Yes (1)

No (0)

Yes (1)

-

IS-S

PA21

Signalling of high/low temperature alarms

on the alarm relay

yes (1)

No (0)

Yes (1)

-

IS-S

PA23

Signalling fire/smoke on alarm relay

Yes (1)

No (0)

Yes (1)

-

IS-S

PA25

Signals RTC alarm on alarm relay

Yes (1)

No (0)

Yes (1)

-

IS-S

PA27

Signals probe alarms on alarm relay

Yes (1)

No (0)

Yes (1)

-

IS-S

VARIOUS PARAMETERS

PH01

Minimum temperature value

-15.0

-20.0

-4.0

PH02

°C

°F

IS-V

PH02

Maximum temperature value

95.0

PH01

110.0

230.0

°C

°F

IS-V

PH03

Minimum CO

2

probe PPM value

0

0

PH04

ppm

IS-V