4 restore the (factory) default parameters, 5 last maintenance operation date – EVCO EPU2BXP1S1 User Manual
Page 44
![background image](/manuals/675315/44/background.png)
EVCO S.p.A.
c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104
EVCO
page 44 of 68
6.4
Restore the (factory) default parameters
Via the “Parameters Reset” procedure it is possible to bring back the system parameters to the default value. The
procedure can only be activated with machine in OFF mode
Enter the Installer ->Various Parameters -> Default menu and press the ENTER key.
Set the PH99 parameter to “YES”(1) and wait until it becomes “NO”(0) again on the display. The system automatically
restores all parameters’ default values.
Note: After this operation switch OFF and back ON power supply to the board to prevent for
malfunctioning.
6.5
Last maintenance operation date
From the Installer->Maintenance menu, press RIGHT until reaching the following mask:
Positioning the cursor on the “Update” writing and pushing the Enter key the old date relevant for the previous
maintenance will be overwritten with the present date updating the PM90 parameter.