8.

MODBUS VARIABLES

The controller can be managed by a supervisor via Modbus protocol. The communication takes place via optional

TTL/RS485 serial interface outside the controller. The various states/parameters exported from the controller are

shown below.

8.1

ModBus exporting table

REGISTER VARS LIST

Addr

Base 0

Addr

Base

1

Name

Value

Min

Max

Description

Mode BMS

0x0100

257

Packed_DI

0

0

65535

Bit1=DI1, Bit2=DI2,
Bit3=DI3, ...,
Bit13=DI13,
Bit14=DI14

R/W

0x0180

385

Packed_DO

0

0

65535

Bit1=DO1, Bit2=DO2,
..., Bit13=DO13,
Bit14=DO14

R/W

0x0200

513

AI01_Antireeze_Probe

0.0

-3276.8

3276.7

R/O

0x0201

514

AI02_AirSupply_Probe

0.0

-3276.8

3276.7

R/O

0x0202

515

AI03_AirReturn_Probe

0.0

-3276.8

3276.7

R/O

0x0203

516

AI04_AirExternal_Probe

0.0

-3276.8

3276.7

R/O

0x0204

517

AI07_CO2_Probe

0

-32768

32767

R/O

0x0205

518

AI08_Press1_Probe

0

-32768

32767

R/O

0x0206

519

AI09_Press2_Probe

0

-32768

32767

R/O

0x0281

642

AO01_Heaters

0.00

0.00

100.00

R/O

0x0282

643

AO02_Heating

0.00

0.00

100.00

R/O

0x0283

644

AO03_ByPass

0.00

0.00

100.00

R/O

0x0284

645

AO04_ReturnFan

0.00

0.00

100.00

R/O

0x0285

646

AO05_SupplyFan

0.00

0.00

100.00

R/O

0x0286

647

AO06_Recyclage

0.00

0.00

100.00

R/O

0x0300

769

PackedAlarm_1

0

0

65535

Bit1=AL01,
Bit2=AL02,
Bit3=AL03,
Bit4=AL04,
Bit5=AL05,
Bit6=AL06,
Bit7=AL07, Bit8=free,
Bit9=AL09,
Bit10=AL10,
Bit11=AL11,
Bit12=AL12,
Bit13=AL13,
Bit14=AL14,
Bit15=AL15,

R/W