beautypg.com

3 automatic regulation with presence sensor, 4 fans thermal overload, 5 fans status – EVCO EPU2BXP1S1 User Manual

Page 47: 6 fans running hours, 2 recovery heat exchanger anti-freeze protection

background image

EVCO S.p.A.

c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104

EVCO

page 47 of 68

6.7.1.3

Automatic regulation with presence sensor

In addition to the previous regulation rules it is possible to modify the working Speed/capacity on the basis of a

presence sensor. If the presence sensor is active (indicating there is someone inside the room), during the COMFORT

time band the fans Speed/capacity is forced to the value set on parameter PF12.

6.7.1.4

Fans thermal overload

Via the digital inputs DI3/DI4 Supply/Return fans thermal overload protection it is possible to enable the thermal

overload alarm of each fan. The alarms are signalled after a fixed delay of 2 seconds and have automatic reset. The

alarms are enabled setting PA03=1. If this is not the case, the thermal overload alarms of the two fans are disabled.

The activation of the thermal overload alarm switches OFF the unit bringing it to the OFF due to alarm status.

6.7.1.5

Fans status

Each of the two fans can be in the following working states:

1.

OFF: the fan is OFF.

2.

ON V1: the fan is ON at speed 1.

3.

ON V2: the fan is ON at speed 2.

4.

ON V3: the fan is ON at speed 3.

5.

Switch-ON stand-by: the fan is to be switched-on. Timing is in progress, e.g. stand-by due to pre-start of the

outside air damper. The status shows the switch-on stand-by for each of the individual speeds.

6.

Switch-OFF stand-by: the fan is to be switched-off. Timing is in progress, e.g. in the case of post-ventilation.

7.

Alarm: the fan is in alarm conditions due to thermal overload.

Reaching of the individual speed in switch-ON can be delayed via the parameter PF06. If PF06=0 switch-ON/OFF is

immediate.

6.7.1.6

Fans running hours

Each fan has an associated variable that counts the number of running hours (Supply fan parameter PM02, Return fan

parameter PM03). The running hours can be zeroed by resetting the relevant parameter.

If the running hours set in the PM01 parameter are exceeded, an alarm is given indicating fan running hours exceeded

(alarms AL09, AL10).

6.7.2

Recovery heat exchanger anti-freeze protection

A probe measures the temperature T of the exhaust air after the recovery heat exchanger on the extraction circuit.

The critical defrosting temperature Tg (can be set by parameter PF07) is fixed by default at 0 °C. Considering the risk

of frost in the recovery heat exchanger when T Tg it is necessary to take some action for protecting the exchanger

when this temperature level is reached. To use this function the PG06 parameter must be enabled (by default it is

always enabled).

There are two possible strategies depending on the presence of the by-pass damper of the recuperator (PG01

parameter).

Note: If the anti-freeze temperature probe is in error conditions, this regulation is not enabled and the fans are

regulated exclusively on the basis of the PF01 parameter.

This manual is related to the following products: