c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104
EVCO
page 40 of 68
PA24
RTC alarm enabling
Active (1)
Not-
active
(0)
Active
(1)
-
CO-S
PA26
Probes alarms signals delay
10
0
240
Sec
CO-S
PA51
Type of alarm fire/smoke
0: Not-active
1: Off by allarm
2: Forcing 1
3: Forcing 2
1
0
3
-
CO-S
VARIOUS PARAMETERS
PH11
Board Modbus address
1
1
247
-
CO-V
PH12
Communication Baud Rate for the board
(0=1200, 1=2400, 2=4800, 3=9600,
4=19200)
3
0
4
-
CO-V
PH13
ModBus Parity (0=none, 1=Odd, 2=Even)
2
0
2
-
CO-V
PH14
Stop Bit ModBus (0=1bit, 1=2bit)
0
0
1
-
CO-V
PH40
Enable outlet temperature probe
Yes (1)
No (0)
Yes (1)
-
CO-V
PH41
Enable return temperature probe
Yes (1)
No (0)
Yes (1)
-
CO-V
PH42
Enable CO
2
probe
No (0)
No (0)
Yes (1)
-
CO-V
PH43
Enable outside air temperature probe
Yes (1)
No (0)
Yes (1)
-
CO-V
PH44
Enable pressure probes
0: Not-active
1: probe 1
2: probe 2
0
0
2
-
CO-V
PH45
CO
2
sensor probe
0: 0-20mA
1: 4-20mA
2: 0-5V
3: 0-10V
0-10V (3)
0-20mA
(0)
0-10V
(3)
-
CO-V
PH46
Pressure sensor probes
0: 0-20mA
1: 4-20mA
2: 0-5V
3: 0-10V
0-10V (3)
0-20mA
(0)
0-10V
(3)
-
CO-V
PH47
Analog output-type electric heaters
0: 0-10V
1: PWM
0-10V (0)
0-10mA
(0)
PWM (1)
-
CO-V
PH51
Logic of the digital input DI1
N.O. (0)
N.O. (0)
N.C. (1)
-
CO-V
PH52
Logic of the digital input DI2
N.O. (0)
N.O. (0)
N.C. (1)
-
CO-V
PH53
Logic of the digital input DI3
N.C. (1)
N.O. (0)
N.C. (1)
-
CO-V
PH54
Logic of the digital input DI4
N.C. (1)
N.O. (0)
N.C. (1)
-
CO-V
PH56
Logic of the digital input DI5
N.C. (1)
N.O. (0)
N.C. (1)
-
CO-V
PH57
Logic of the digital input DI6
N.O. (0)
N.O. (0)
N.C. (1)
-
CO-V
PH58
Logic of the digital input DI7
N.C. (1)
N.O. (0)
N.C. (1)
-
CO-V
PH59
Logic of the digital input DI8
N.O. (0)
N.O. (0)
N.C. (1)
-
CO-V
PH60
Logic of the alarm relay DI9
N.O. (0)
N.O. (0)
N.C. (1)
-
CO-V
PH61
Logic of the alarm relay DO12
N.O. (0)
N.O. (0)
N.C. (1)
-
CO-V