EVCO EPU2BXP1S1 User Manual
Page 17

EVCO S.p.A.
c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104
EVCO
page 17 of 68
3.2.2
I/O Configuration with 1 speed fans + speed variator
c-pro 3 micro SAVE/ c-pro 3 kilo SAVE
I/O
Description
Analogue inputs
AI 1
Anti-freeze Temperature Probe (Recovery heat exchanger By-Pass) - NTC
AI 2
Supply Air Temperature Probe - NTC
AI 3
Return Air Temperature Probe - NTC
AI 4
Outdoor Air Temperature Probe - NTC
AI 5
Not used
AI 6
Not used
AI 7
CO
2
probe (0-10 V) (Optional)
AI 8
Pressure probe 1 (0-10 V) (Optional)
AI 9
Pressure probe 2 (0-10 V) (Optional)
Serial ports
RS485
RS485 Modbus RTU
CAN bus
To Vgraph
Digital inputs
DI 1
Presence sensor
DI 2
Start – Stop (remote)
DI 3
Supply fan thermal overload (protection)
(3 in series)
DI 4
Return fan thermal overload (protection)
(3 in series)
DI 5
Differential pressure switch
DI 6
Hot water coil anti-freeze thermostat
DI 7
Fire/Smoke
DI 8
Outside air damper limit switch (full open)
DI 9
Outside air damper limit switch (full closed)
Analogue outputs
AO 1
Not used
AO 2
Hot water coil modulating valve control (0-10 V)
AO 3*
Recovery heat exchanger BY-PASS damper control (0-10 V)
AO 4
Return fan control signal (0-10 V)
AO 5
Supply fan control signal (0-10 V)
AO 6
Mixing room damper control (0-10 V)
Digital Outputs (Relay)
DO 1
Return fan (speed 0)
DO 2
Supply fan (speed 0)
DO 3
Not used
DO 4
Electric heaters step 1
DO 5
Electric heaters step 2
DO 6
Electric heaters step 3
DO 7*
Recovery heat exchanger BY-PASS damper
DO 8
Outdoor air damper
DO 9
Generic alarm (can be configured)
(*) The recovery heat exchanger BY-PASS damper control can be analogic or digital, and
setting with clock