EVCO EPU2BXP1S1 User Manual
Page 35

EVCO S.p.A.
c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104
EVCO
page 35 of 68
Working
Working
Not Working
PT17
Saturday
0
Working
0
Working
1
Not Working
OR
MAINTENANCE
PM01
Functioning hours maximum limit for fans.
The relevant alarm will be triggered over
this limit
8000
0
100000
Hours
IS-MA
PM02
Outlet fan functioning hours
0
0
100000
Hours
IS-MA
PM03
Return fan functioning hours
0
0
100000
Hours
IS-MA
PM90
Last date on which maintenance was
performed on the machine
IS-MA
PM11
Calibration of the anti-freeze air
temperature probe
0.0
-10.0
-18.0
10.0
18.0
°C
°F
IS-MA
PM12
Calibration of the outlet air temperature
probe
0.0
-10.0
-18.0
10.0
18.0
°C
°F
IS-MA
PM13
Calibration of the return air temperature
probe
0.0
-10.0
-18.0
10.0
18.0
°C
°F
IS-MA
PM14
Calibration of the CO
2
probe
0.0
-200
200
ppm
IS-MA
PM15
Calibration of the outside air introduction
temperature probe
0.0
-10.0
-18.0
10.0
18.0
°C
°F
IS-MA
PM16
Calibration of the pressure probe 1
0.0
-200
200
ppm
IS-MA
PM17
Calibration of the pressure probe 2
0.0
-2000
2000
Pa
IS-MA
FANS
PF00
Type of fans control:
0: Speed
1: Capacity
0
0
1
-
IS-F
PF01
Type of fans regulation:
0: Manual
1: Automatic
2: Automatic with presence sensor
3: Automatic with CO
2
sensor
0
0
3
-
IS-F
PF03
Fans Speed/Capacity in COMFORT period
V2
V1
V3
-
IS-F
PF04
Fans Speed/Capacity in ECONOMY period
V1
V0
V2
-
IS-F
PF05
Fans Speed/Capacity in RTC error
V0
V0
V3
-
IS-F
Only if
PF01=1/2/3
PF12
Fans Speed/Capacity in COMFORT with
presence sensor active
V3
V1
V3
-
IS-F
PF13
Speed/Capacity in case of « non working »
day
V0
V0
V3
-
IS-F
PF14
Set point CO
2
probe
500
PH03
PH04
ppm
IS-F
PF15
Proportional band CO
2
probe
600
0
1000
ppm
IS-F
PF16
Type of CO
2
regulation
0
0
1
IS-F
If PF00=1
PF16=1
PF17
Integral time CO
2
regulation
0
0
300
sec
IS-F
PF21
Speed variator value corresponding to speed V1
33.50
0.00
100.00
%
IS-F