5 heating, 1 heating with hot water coil – EVCO EPU2BXP1S1 User Manual

Page 52

background image

EVCO S.p.A.

c-pro 3 micro SAVE/ c-pro 3 kilo SAVE | Application Manual ver. 1.0 | Code 144CP3UKSAE104

EVCO

page 52 of 68

Note: If one of the probes is involved in the regulation error in the adjustment of the free-heating is no longer usable

and the ramp of the heating rule on the total of the control differential.

If the adjustment is used for changing the air at the request of a specific probe of CO2 according to the control probe,

the setpoint (PS20) and to the relative differential (PS21) is actuated damper.

Note: If the air quality sensor is in error adjustment is inhibited.

6.8.5

Heating

The COMPLETE solution offers the possibility to use a hot water coil or a set of three electric heaters for space heating

purpose. By setting the PG02 parameter the desired resource is activated along with the relevant alarms connected.

For using this function it is necessary to enable the supply temperature probe setting PH40=1.

During the anti-freeze protection of the recovery heat exchanger, on units without by-pass, the heating source must

be deactivated for protection. The heating source is disabled with a delay defined at the parameter PF09 after the fan

speed has reduced to V1 during the supply fan speed decrease for antifreeze protection. If the antifreeze condition

remains active for further PF09 the supply fan is stopped.

6.8.5.1

Heating with hot water coil

To use the hot water coil for space heating it is required to set the parameter PG02=1. The control is based on the

supply temperature via a supply Set Point (SPHM parameter) and a relevant differential (Pb02 parameter). The coil is

controlled via a proportional-integral algorithm (PI). The control can be only proportional by setting the integral time

Pb03=0.

Set

Point

Temperature

Pb02

Pb02 / 2

100 %

0 %

Heating

Free-heating

SPHM: Set

0%

Supply

Pb02: Diff

100%