7.1
Manual and automatic reset alarms
As shown previously there are two types of alarm. Those with manual reset and those with automatic reset. For some
alarms it is possible to set (Alarms Reset) the most suitable type of reset for user needs by means of the relevant
parameters. Other alarms have predetermined reset type.
7.1.1
Manual reset alarms
If a manual rest alarm occurs the alarm icon starts to flash and the buzzer is activated (if configured PH20=1).
Once the conditions for which the alarm has occurred are reset it is possible to manual reset the alarm. To perform
this operation:
⋅
Enter the relevant alarm page
⋅
hold the ENTER key down for about 2 seconds.
At this point, if there are no other active alarms, the page indicating “NO ALARMS” will be displayed, the icon
disappears, the buzzer switches off and the unit starts working normally. If there are other active alarms the page
relevant to the next active alarm will be displayed.
The consequences relevant to an active manual reset alarm remain valid until the user reset the alarm message.
7.1.2
Automatic reset alarms
If an automatic reset alarm occurs the alarm icon starts to flash and the buzzer is activated (if configured PH20=1).
Once the conditions for which the alarm occurred are reset the alarm message and the relevant consequences are
reset automatically without need of user intervention.
7.2
Alarms table
Below is a list of all alarms managed by the application. The order of presentation is the same as the order of active
alarms occurrence. The alarms can be displayed also with the machine in OFF status.
Code
Alarm description
Reset
Consequence
Delay
AL01
Supply fan thermal overload
(*1)
Automatic
Switches all devices off
Fixed 2 s
AL02
Return fan thermal overload
(*1)
Automatic
Switches all devices off
Fixed 2 s
AL03
Differential pressure switch
(*1)
Manual
Switches all devices off
Selectable
AL04
Hot water coil anti-freeze
Automatic
-
Open the hot water valve
completely
-
Close the fresh air damper
-
Switches fans OFF
Selectable
AL05
Electric heaters thermal overload – manual
reset
Manual
Switches the heaters OFF
Fixed 2 s
AL06
Outside air damper limit switch “completely
open”
(*1)
Manual
Switches all devices off
Selectable
Outside air damper limit switch “completely
closed”
(*1)
AL07
Electric heaters thermal overload – automatic
reset
Automatic
Switches the heaters OFF
Selectable
AL09
Supply fan running hours
Manual
(*2)
Signalling only
-
AL10
Return fan running hours
Manual
(*2)
Signalling only
-