PH04
Maximum CO
2
probe PPM value
1100
PH03
10000
ppm
IS-V
PH05
Enables unit switch-on/off from
“Start/Stop” digital input
Yes (1)
No (0)
Yes (1)
-
IS-V
PH06
Enables unit switch-on/off from supervisor
No (0)
No (0)
Yes (1)
-
IS-V
PH07
Minimum value Pa pressure probe
0
0
32000
Pa
IS-V
PH08
Maximum value Pa pressure probe
3000
0
32000
Pa
IS-V
PH18
Clear hystorical alarms
NO (0)
NO (0)
YES (1)
-
IS-V
Set YES (1)
ad wait for
the NO (0)
PH20
Enable buzzer
Yes (1)
No (0)
Yes (1)
-
IS-V
PH30
Temperature unit of measurement
0: °Celsius
1: °Fahrenheit
0 (°C)
0 (°C)
1 (°F)
-
IS-V
PH32
Language of user interface
(English, Italian, French)
ENG
ENG
FRE
-
IS-V
PH99
Reset the factory parameters default
NO (0)
NO (0)
YES (1)
-
IS-D
Wait for the
NO (0)
value to be
read again
on reset
completion
PSd2
Installer level password (2)
0
-999
9999
-
IS
Level 3
MANUFACTURER MENU
CONFIGURATION PARAMETERS
After modification of these parameters it is recommended to remove and then re-apply the power supply to the board.
PG00
Unit type:
1=Compact
2=Complete
2
1
2
-
CO-G
PG01
Enabling bypass recuperation
Yes (1)
No (0)
Yes (1)
-
CO-G
PG02
Selection of type of device for heating:
0: Disabled
1: Hot water coil only
2: Electric heater DO coil only
3: Electric heater AO coil only
3
0
3
-
CO-G
PG03
Type of recovery heat exchanger by-pass
damper control:
0: Digital Control (DO7)
1: Analogue Control (AO3)
DO (0)
DO (0)
AO (1)
-
CO-G
PG04
Outside air damper enabling
Yes (1)
No (0)
Yes (1)
-
CO-G
PG05
Enabling of post-ventilation
Yes (1)
No (0)
Yes (1)
-
CO-G
PG06
Enabling of recovery heat exchanger anti-
freeze protection
Type 1
(1)
Disabled
(0)
Type 2 (2)
-
CO-G
PG08
Enabling of recovery heat exchanger by-pass
in summer
Yes (1)
No (0)
Yes (1)
CO-G
PG09
Activation of outside air damper end run
Yes (1)
No (0)
Yes (1)
CO-G
PG10
Type of fan
DO (0)
DO (0)
AO (1)
-
CO-G
If PF00=1
PG10=1