5.
Configuration parameters
Below are listed all parameters managed by the application. A brief description, the range of acceptable values, unit of
measurement, the default value proposed and the menu in which it is found is supplied for every parameter. The
menus are structured following this logic:
⋅
UT: user menu
⋅
IS: installer menu
o
OR: Clock branch installer menu
o
IS-MA: maintenance branch installer menu
o
IS-F: fans branch installer menu
o
IS-B: heating coils branch installer menu
o
IS-SE: outside air damper branch installer menu
o
IS-FC: Free Cooling branch installer menu
o
IS-S: safety device branch installer menu
o
IS-V: various parameters branch installer menu
o
IS-D: default branch installer menu
⋅
C O: manufacturer menu
o
CO-G Configuration branch manufacturer menu
o
CO-F Fans branch manufacturer menu
o
CO-B Heating coils branch manufacturer menu
o
CO-SE Outside air damper branch manufacturer menu (free-cooling)
o
CO-RH Recovery heat exchanger branch manufacturer menu
o
CO-S Safety branch manufacturer menu
o
CO-V Various branch manufacturer menu
5.1
COMPACT solution list of configuration parameters
Code
Parameter description
Default
Min
Max
UM
Menu
Notes
Level 1
USER MENU
USER
PF02
Fans speed/Capacity in manual regulation
mode
V3
V0
V3
UT
Only if
PF01=0
(Manual
Regulation)
PSd1
User level password (1)
0
-999
9999
-
UT
Level 2
INSTALLER MENU
CLOCK
PT01
Start of the COMFORT time period
08:00:00
00:00:00
23:59:59
-
OR
PT02
Start of the ECONOMY time period
20:00:00
00:00:00
23:59:59
-
OR
PT11
Sunday
0
Working
0
Working
1
Not Working
OR
PT12
Monday
0
Working
0
Working
1
Not Working
OR
PT13
Tuesday
0
Working
0
Working
1
Not Working
OR