PF10
Differential for the by-pass of the recovery
unit damper in anti-freeze protection
mode
2.0
0.0
20.0
36.0
°C
°F
CO-F
PF11
Fans working time in post-ventilation
mode
30
0
999
Sec
CO-F
OUTSIDE AIR DAMPER
This menu is only accessible if PG04=1
PS01
Fans switch-on delay from outside air
damper activation
45
0
999
Sec
CO-SE
Reading
only
PS02
Outside air damper switch-OFF delay from
fans switch-off
15
0
999
Sec
CO-SE
PS05
Delay of outside air damper end run
60
0
999
Sec
CO-SE
PS06
Enable FreeHeating
0: No
1: Yes
No (0)
No (0)
Yes (1)
CO-SE
PS07
Type damper control mixing room
0: Free-Heating only
1: Regulating air quality only
2: Priorities on demand higher of the two
3: Average of the two requests
4: Fixed open
0
0
4
CO-SE
PS08
Minimum aperture shutter
mixing room
20.0
0.0
PS09
%
CO-SE
PS09
Maximum aperture shutter mixing
chamber
100.0
PS08
100.0
%
CO-SE
PS10
Fixed value of damper opening
50.0
0.0
100.0
%
CO-SE
PS12
Differential which enables free-cooling
and free-heating temperature
2.0
0.0
20.0
°C
CO-SE
PS13
Setpoint differential which enables free-
cooling and free-heating temperature
4.0
0.0
20.0
°C
CO-SE
PS15
Opening the minimum and maximum
damper
0:
Disabled
1: Only internal bandwidth
2: Always
2
0
2
CO-SE
PS20
Setpoint - adjusting the air quality
600
0
10000
ppm
CO-SE
PS21
Differential - adjusting the air quality
100
0
2000
ppm
CO-SE
RECOVERY HEAT EXCHANGER
Pr01
Anti-freeze temperature minimum
setpoint
1.0
PH01
PH02
°C
°F
CO-RH
Used only if
PG06 = 2
Pr02
Anti-freeze temperature minimum
differential
2.0
0.0
0.0
20.0
36.0
°C
°F
CO-RH
Pr03
Recovery heat exchanger by-pass cycle
time for cyclical defrosting
5
1
99
Min
CO-RH
ALARM PARAMETERS
PA03
Enabling of supply/return fans thermal
overload alarm
Active
(1)
Not-active
(0)
Active (1)
-
CO-S