EVCO EVF328J9 User Manual
Page 48
EVCO S.p.A.
EVF 300 series | Installer manual ver. 1.1 | Code 144F300E114
Page 48 of 62
16
ALARMS
16.1
Alarms
The following table illustrates the meaning of the device alarm codes.
CODE
MEANING
AH1
if the parameter CFG is set at 0, temperature
solutions:
-
check the chamber temperature; see parameters A1 and A3
main consequences:
- no
consequence
if the parameter CFG is set at 1, top temperature alarm
solutions:
-
check the top temperature; see parameters A1 and A3
main consequences:
- no
consequence
AH2
floor temperature alarm
solutions:
-
check the top temperature; see parameters A1 and A3
main consequences:
- no
consequence
Ht
Use temperature alarm.
solutions:
-
check the use temperature of the control module; see parameter P7
-
when the cause of the alarm disappears, press and release a key
main consequences:
-
the device will be switched off
-
the technical compartment fan will be on (only if parameter u11 is set at 0) and the remaining
outputs will be off
dr
door micro switch input alarm
solutions:
-
check the causes of the activation of the input; see parameters i0 and i1,
main consequences:
-
the effect established with parameter i0
AL1
circuit breaker protection input alarm
solutions:
-
check the causes of the activation of the input; see parameter i11,
main consequences:
-
if the alarm occurs when the device is on, a cooking cycle cannot be started
-
if the alarm occurs during a cooking cycle, the cycle will be interrupted
-
steam injection will be disables, the steam generator, to top output and the floor output will be
switched off