EVCO EVF328J9 User Manual
Page 38
![background image](/manuals/675278/38/background.png)
EVCO S.p.A.
EVF 300 series | Installer manual ver. 1.1 | Code 144F300E114
Page 38 of 62
CFG
0
1
- - -
0
1
type of operation
0 = with one analogue input (chamber probe, i.e.
with management of the power supplied at the
top and at the floor independently from each
other.)
1 = with two analogue inputs (top and floor probe,
i.e. with management of the temperature of the
top and at the floor independently from each
other.)
PARAM.
MIN.
MAX.
U.M.
INP. 1
INP. 2
ANALOGUE INPUTS
CA1 -25/-50 25/50 °C/°F
(1)
0
0
if CFG = 0, chamber probe offset
if CFG = 1, top probe offset
CA2
-25/-50
25/50
°C/°F (1)
not dis.
0
floor probe offset
CA3
-25/-50
25/50
°C/°F (1)
0
0
steam probe offset
P0
0
1
- - -
0
0
probe type
0 = thermocouple
J
1 = thermocouple
K
P2
0
1
- - -
0
0
temperature unit of measurement (2)
0 =
°C
1 =
°F
P4
0
2
- - -
2
2
steam injection activation consent mode
0 = MANUAL - steam injection will be allowed if the
steam generator has been switched on
1 = REMOTE - steam injection will be allowed if the
steam generator has been switched on and if the
multi-function input has been activated (until
the input is deactivated; only if i5 = 1)
2 = THERMOSTAT - steam injection will be allowed if
the steam temperature adjustment has been
activated and the steam temperature is above
the SPS (until the temperature drops below the
t4 value)
P5
0
1
- - -
0
0
information shown in the top part of the "UPPER" display
when the device is on and when a cooking cycle is in
progress
0 = if CFG = 0, temperature of the chamber
if CFG = 1, top temperature
1 = if CFG = 0, work set-point
if CFG = 1, top set-point