EVCO EVF328J9 User Manual
Page 42

EVCO S.p.A.
EVF 300 series | Installer manual ver. 1.1 | Code 144F300E114
Page 42 of 62
PARAM.
MIN.
MAX.
U.M.
INP. 1
INP. 2
TEMPERATURE ALARMS
A1 0 999
°C/°F
(1)
0 0
if CFG = 0, temperature of the chamber above which the
temperature alarm is activated (code “AH1”); see also
A3 (8)
if CFG = 1, temperature of the top above which the
temperature alarm is activated (code “AH1”); see also
A3 (8)
A2 0 240 min 0 0
if CFG = 0, temperature alarm display (code “AH1”)
if CFG = 1, top temperature alarm delay (code “AH1”)
A3
0
2
- - -
0
0
if CFG = 0, temperature alarm type (code “AH1”)
if CFG = 1, top temperature alarm type (code “AH1”)
0 = no alarm
1 = absolute (i.e. A1)
2 = if CFG = 0, relative to the work set-point (i.e.
“work set-point + A1”)
if CFG = 1, relative to the top set-point (i.e. “top
set-point + A1”)
A4 0 999
°C/°F
(1)
not
dis.
0
temperature of the floor above which the floor
temperature alarm is activated (code “AH2”); see also
A6 (8)
A5
0
240
min
not dis.
0
floor temperature alarm delay (code “AH2”)
A6
0
2
- - -
not dis.
0
type of floor temperature alarm (code “AH2”)
0 = no alarm
1 = absolute (i.e. A4)
2 = relative to the floor set-point (i.e. “floor set-
point + A4”)
PARAM.
MIN.
MAX.
U.M.
INP. 1
INP. 2
DIGITAL INPUTS