EVF815 | Installer manual ver. 1.2 | Code 144F815E124

page 55 of 60

supplied from the control
module.

115... 230 VAC (±15%),
50/60 Hz (±3 Hz), 10 VA max.

Overvoltage category:

III.

Clock:

incorporated (with condenser).

Battery autonomy in the event of a power-cut: 24 h with battery
fully charged.

Battery charging time: 2 min (the battery is charged by the device
power supply).

Signal buzzer and alarm:

incorporated.

Analogue inputs:

3 inputs (cabinet probe, needle probe and evaporator probe), can
be set via configuration parameter for PTC/NTC probes

PTC type analogue inputs (990 Ω @ 25°C, 77°F)
Type of sensor:

KTY 81-121.

Field of measurement:

from -50 to 150°C (from -58 to 302°F).

Resolution:

0.1 °C (1 °F).

Protection: none.

NTC type analogue inputs (10K Ω @ 25°C, 77°F)
Type of sensor:

ß3435.

Field of measurement:

from -40 to 105°C (from -40 to 220°F).

Resolution:

0.1 °C (1 °F).

Protection: none.

Digital inputs:

2 inputs (door micro switch and high pressure), which can be set
via configuration parameter due to normally open contact/normally
closed contact (free of voltage contact, 5 VDC, 2 mA)

Digital inputs
Power supply:

none.

Protection: none.

Displays:

custom 4 digit display, with function icon.