EVCO EVF815P9 User Manual
Page 31
EVCO S.p.A.
EVF815 | Installer manual ver. 1.2 | Code 144F815E124
page 31 of 60
P0
0
1
- - - -
0
probe type
0 = PTC
1 = NTC
P1
0
1
- - - -
1
°C decimal point
1 = yes
P2
0
1
- - - -
0
temperature unit of measurement (2)
0 = °C
1 = °F
P3
0
1
- - - -
1
enabling the needle probe
1 = yes
P4
0
1
- - - -
1
enabling the evaporator probe
1 = yes
P8 0 250 ds
5
delay displaying temperature variation detected by the
probes
P9
0
2
- - - -
1
type of backlight
0 = off during “on” status and during the “run” status
and with START/STOP key low light intensity during
the “stand-by” status
1 = with low light intensity during the “on” status and
during the "run" status and with START/STOP key
low light intensity during the “stand-by” status
2 = with high light intensity during the “on” status and
during the "run" status and with START/STOP key
high light intensity during the “stand-by” status
Par.
Min.
Max.
Unit
Default
Main regulator
r0
0.1
15.0
°C/°F (1)
2.0
parameters differential r7, r8, r9, r10, r11 and r12
r1
1
500
min
90
duration of time-controlled blast chilling
r2
1
500
min
240
duration of time-controlled deep freezing
r3 -50.0 99.0 °C/°F
(1)
3.0
temperature-controlled blast chilling end time temperature;
also end temperature of the temperature-controlled soft
deep freezing phase (temperature detected by the needle
probe); see also parameter r5
r4 -50.0 99.0 °C/°F
(1) -18.0
temperature-controlled deep freezing end temperature
(temperature detected by the needle probe); see also
parameter r6