EVCO EVF815P9 User Manual
Page 23
EVCO S.p.A.
EVF815 | Installer manual ver. 1.2 | Code 144F815E124
page 23 of 60
5.1
If parameter r19 is set at 0, the display will show the work set-point during deep freezing; this value can also
be set via parameter r8.
If parameter r21 has value 1 and it has been decided to start the cycle with timed-control, the display will show
the duration of time-controlled deep freezing; this value can also be set via parameter r2.
5.2
If parameter r19 is set at 1, the display will show the deep freezing end temperature; this value can also be set
via parameter r4.
If parameter r21 has value 1 and it has been decided to start the cycle with timed-control, the display will show
the duration of time-controlled deep freezing; this value can also be set via parameter r2.
5.3
Press and release the UP or DOWN key within 15 s to modify the parameter value:
6.
Press and release the START/STOP key: the LED and the
LED will remain permanently on and the test
to verify the correct insertion of the needle probe will be started; see paragraph 6.7 " Test for verification of the
correct insertion of the needle probe".
If parameter r21 has value 1 and it has been decided to start the cycle with timed-control, also the will
remain permanently on and the cycle will be started with timed-control.
6.1
If the test is completed successfully, the cycle will be started.
The maximum deep freezing duration count is started on condition that the temperature detected by the
needle probe is below that established with parameter r15.
6.2
If the test is not completed successfully, the cycle will be started with timed-control.
During soft deep freezing, the display shows the residual time of the deep freezing duration and the
LED is on.
To modify the residual time, operate as indicated:
6.2.1
Press and release the UP or DOWN key again to modify the time value: the display will flash.
6.2.2
Do not operate for 4 s: the display will stop flashing and remain on permanently.
The successive parameters establish the following values:
-
parameter r8 establishes the work set-point during deep freezing
-
parameter r14 establishes soft deep freezing phase duration.
During deep freezing, the display shows the residual time of the deep freezing duration and the LED
is on.
The successive parameters establish the following values:
-
parameter r2 establishes deep freezing duration
-
parameter r8 establishes the work set-point during deep freezing.
Operate as indicated to stop the cycle:
7.
Hold the START/STOP key down.
During soft deep freezing, the display shows the temperature detected by the needle probe and the
LED is on.
The successive parameters establish the following values:
-
parameter r3 establishes deep freezing soft phase end temperature.
-
parameter r6 establishes the maximum deep freezing duration
-
parameter r7 establishes the work set-point during the deep freezing soft phase.
To display the cabinet temperature, press and release the BLAST CHILLING, DEEP FREEZING or the HARD/SOFT key;
to restore the normal display, press and release the same key again or do not operate for 15 s.
When the temperature detected by the needle probe reaches the end temperature of the soft phase, the device
automatically passes to deep freezing.
During deep freezing, the display shows the temperature detected by the needle probe and the
LED is on.
The successive parameters establish the following values:
-
parameter r4 establishes the deep freezing end temperature
-
parameter r6 establishes the maximum deep freezing duration
-
parameter r8 establishes the work set-point during deep freezing