EVCO EVF815P9 User Manual

Page 36

background image

EVCO S.p.A.

EVF815 | Installer manual ver. 1.2 | Code 144F815E124

page 36 of 60

d16 0 99

min

0

duration of pre-dripping (only if parameter d1 is set at 1;
the compressor and evaporator fan will be off during pre-
dripping and the defrosting output will remain activated)

Par.

Min.

Max.

Unit

Default

Temperature alarms (8) (9)

A1 0.0 99.0 °C/°F

(1) 10.0

cabinet temperature below which the minimum temperature
alarm is activated (relative to the work set-point, i.e. “r10 -
A1” during post blast chilling storage and “r11 - A1” during
post deep freezing storage; (“AL” code); see also
parameter A11 (4)

A2

0

1

- - - -

1

enabling of minimum temperature alarm (“AL” code)
1 = yes

A4 0.0 99.0 °C/°F

(1) 10.0

cabinet temperature above which the maximum
temperature alarm is activated (relative to the work set-
point, i.e. “r10 +A4” during post blast chilling storage and
“r11 +A4” during post deep freezing storage; (“AH” code);
see also parameter A11 (4)

A5

0

1

- - - -

1

enabling of maximum temperature alarm (“AH” code)
1 = yes

A7 0 240 min

15 temperature

alarm

delay(“AL” code and “AH” code)

A8 0 240 min

15

maximum temperature alarm delay (“AH” code) from the
conclusion of evaporator fan stop and storage start-up

A10 0 240 min

5

duration of a power cut such to cause the power cut alarm
to be memorised ( “PF” code)when the power is supplied
0 = the alarm will not be signalled

AA 0 240

s

5

duration of buzzer activation on conclusion of blast chilling
and deep freezing

A11

0,1

15,0

°C/°F (1)

2,0

parameters A1 and A4 differential