EVF815 | Installer manual ver. 1.2 | Code 144F815E124

page 32 of 60

r5 1 500 min

90

maximum duration of temperature-controlled blast chilling;
see parameter r3 also

r6 1 500 min

240

maximum duration of temperature-controlled deep
freezing; see parameter r4 also

r7 -50.0 99.0 °C/°F

(1)

0.0

work set-point during blast chilling; also work set-point
during the soft deep freezing phase (cabinet temperature);
see also parameter r0

r8 -50.0 99.0 °C/°F

(1) -40.0

work set-point during deep freezing (cabinet temperature);
see also parameter r0

r9 -50.0 99.0 °C/°F

(1) -20.0

work set-point during hard blast chilling phase (cabinet
temperature); see also parameter r0

r10 -50.0 99.0 °C/°F

(1)

2.0

work set-point during post blast chilling storage (cabinet
temperature); see also parameter r0

r11 -50.0 99.0 °C/°F

(1) -20.0

work set-point during post deep freezing storage (cabinet
temperature); see also parameter r0

r12 -50.0 99.0 °C/°F

(1)

5.0

work set-point during pre-cooling (cabinet temperature);
see also parameter r0

r13 -50.0 99.0 °C/°F

(1)

15.0

end temperature of the temperature-controlled hard blast
chilling phase (temperature detected by the needle probe)

r14 10 100

%

60

duration of the time-controlled hard blast chilling phase
(intended as a percentage of the value established with
parameter r1); also duration of the time-controlled soft
deep freezing phase (intended as a percentage of the value
established with parameter r2)

r15 -50.0 99.0 °C/°F

(1)

65.0

temperature below which the count of the maximum
temperature-controlled blast chilling and maximum
temperature-controlled deep freezing is started
(temperature detected by the needle probe)

r16

0

2

- - - -

1

type of operating cycle that can be selected
0 = blast chilling and storage
1 = blast chilling and storage or deep freezing and

storage

2 = deep freezing and storage