EVF815 | Installer manual ver. 1.2 | Code 144F815E124

page 40 of 60

Lb

0

3

- - - -

2

baud rate
0 = 2,400

baud

1 = 4,800

baud

2 = 9,600

baud

3 = 19,200

baud

LP

0

2

- - - -

2

Parity
0 = none (no parity)
1 = odd
2 = even

Par. Min. Max.

Unit

Default Reserved

E9

0

1

- - - -

1

Reserved


Notes:
(1)

the unit of measurement depends on parameter P2

(2)

appropriately set the parameters relative to the regulators after modification of parameter P2

(3)

the time established with the parameter is counted also during the "on" status and during the "stand-by" status

(4)

The parameter differential is 2 °C/4 °F

(5)

defrosting is only enabled during storage, except for defrosting on blast chilling start and deep freezing start,
which can be established using parameter d4

(6)

the device memorises the defrosting interval count every 30 minutes; the modification of parameter d0 has
effect from the conclusion of the previous defrosting interval (or the activation of defrosting in manual mode)

(7)

if on activation of defrosting, the previous compressor switched on at from a time shorter than that established
with parameter d15, the compressor will remain on longer for the fraction of time necessary to complete this
time period

(8)

the temperature alarms are only enabled during storage

(9)

during defrosting. pre-dripping, dripping and evaporator fan standstill, the temperature alarms are not enabled,
on condition that they occurred after activation of defrosting. When the door is open, i.e. if the door micro
switch input is active and the parameter i0 is set at values different to 0, the maximum temperature alarm is
not enabled, on condition that occurred after the door was opened

(10) if parameter P4 is set at 0, during pre-cooling, blast chilling and deep freezing the evaporator fan will be on and

during storing the device will operate as if parameter F2 it were set at 2

(11) the condenser fan operates parallel to the compressor
(12) the door open is enabled only using the "run" state
(13) if the door is opened during defrosting or evaporator fan standstill, opening has no effect on the compressor
(14) modify the parameter during the "stand-by" status to prevent damage to the utility
(15) if parameter u2 is set at 0, device switch-off will cause the cabinet light to switch off and on successive switch

on the cabinet light will remain off. If parameter u2 is set at 1, device switch-off will not cause the cabinet light
to switch off and on successive switch-on the cabinet light stays on.