EVF815 | Installer manual ver. 1.2 | Code 144F815E124

page 35 of 60

d1

0

3

- - - -

1

type of defrosting
0 = electrical (the compressor will be switched off during

defrosting, the defrosting output will be activated
and the evaporator fan will be switched off)

1 = hot gas (the compressor will be switched on during

defrosting, the defrosting output will be activated
and the evaporator fan will be switched off)

2 = air (the compressor will be switched off during

defrosting and the defrosting output will be
activated; the evaporator fan will be switched on,
independently from the conditions of the door, i.e.
independently from the door micro switch input
status)

3 = air with door open (the compressor will be switched

off during defrosting and the defrosting output will
be activated; the evaporator fan will be switched on,
on condition that the door is open, i.e. that is on
condition that the door micro switch is active and
that the parameter i0 is set at values different to 0)

d2 -50.0 99.0 °C/°F

(1)

2.0

defrosting end temperature (evaporator temperature); see
also parameter d3

d3 0 99 min

30

if parameter P4 is set at 0, duration of defrosting
if parameter P4 is s et at 1, maximum duration of
defrosting; see also parameter d2
0 = defrosting will never be activated

d4

0

1

- - - -

0

defrosting on start-up of blast chilling and deep freezing
1 = yes

d5 0 99 min

30

defrosting delay on start-up of storing
0 = defrosting will be started on expiry of the time

established with parameter d0

d7 0 15 min

2

dripping duration (the compressor and the evaporator fan
remain off during dripping and the defrosting output will be
deactivated)

d15 0 99

min

0

minimum duration of compressor switch-on on activation of
defrosting so these can be activated (only if parameter d1 is
set at 1) (7)