12

ERRORS

12.1

Errors

The following table illustrates the meaning of the error codes.

Code

Meaning

Pr1

Cabinet probe error.
Solutions:
-

check the value of the parameter P0

-

check the integrity of the probe

-

check the device-probe connection

-

check the temperature of the cabinet.

Main consequences:
-

if the error occurs during the “stand-by” status, no operating cycles can be selected or started

-

if the error occurs during blast chilling or deep freezing, the cycle will be interrupted

-

if the error occurs during storage, compressor activity will depend on parameters C4 and C5 or
C9

-

defrosting will never be activated

-

the door heating elements will never be switched on

-

the minimum temperature alarm (“AL” code) will never be activated

-

the maximum temperature alarm (“AH” code) will never be activated

Pr2

Needle probe error.
Solutions:
-

the same as the cabinet probe error (“Pr1” code) but relative to the needle probe.

Main consequences:
-

if the error occurs during the “stand-by” status, temperature-controlled operating cycles will be
started by time-control

-

if the error occurs during temperature-controlled blast chilling, this will have duration of the
time set by parameter r1

-

if the error occurs during temperature-controlled deep freezing, this will have duration of the
time set by parameter r2

-

if the error occurs during needle probe heating, this operation will be interrupted.

Pr3

Evaporator probe error.
Solutions:
-

the same as the cabinet probe error (“Pr1” code) but relative to the evaporator probe.

Main consequences:
-

if parameter P4 is set at 1, defrosting will last for the period of time established with parameter
d3

-

if parameter F0 is set at 1, parameter F16 will have no effect

-

if parameter F4 is set at 1, the device will operate as if it were set at 2.