EVF815 | Installer manual ver. 1.2 | Code 144F815E124

page 37 of 60

A13

0

1

- - - -

1

memorisation of the temperature-controlled blast chilling or
temperature-controlled deep freezing non concluded within
maximum duration alarm (“tiME”)
1 = yes

Par.

Min.

Max.

Unit

Default

Evaporator and condenser fan

F0

0

2

- - - -

1

evaporator fan activity during pre-cooling, blast chilling and
deep freezing
0 = off
1 = on; see also parameters F16 and F17
2 = parallel to the compressor; see also parameters F9

and F17

F1 -50.0 99.0 °C/°F

(1) -1.0

evaporator temperature above which the evaporator fan is
off during storage (only if parameter F2 is set at 3); see
also parameter F8(10)

F2

0

3

- - - -

3

evaporator fan activity during storage
0 = off
1 = on
2 = parallel to the compressor; see also parameter F9
3 = on; see also parameter F1

F3 0 15 min

2

duration of evaporator fan standstill (the compressor can be
on during evaporator fan standstill, the defrosting output
will remain deactivated and the evaporator fan will remain
off)

F8

0.1

15.0

°C/°F (1)

2.0

F1, F16 and F17 parameters differential

F9 0 240

s

0

evaporator fan switch-off delay from compressor switch off
(only if parameter F0 and/or parameter F2 are set at 2)

F12 0 240

s

30

condenser fan switch-off delay from compressor switch-off
(11)

F15 0 240

s

15

evaporator fan delay from door closure, i.e. from the
deactivation of the door micro switch input