Monarch Instrument DC 2000 User Manual
Page 92

Page 5-26
Chapter 5 Programming
Programming Parameters - Selecting Log Linear point types requires setting up parameters like regular
Programming linear point types except that the Low and High Exponents must be set in Output Scales. From
the Point Type menu use the UP (
↑) or DOWN (↓) Arrow Keys to highlight “Log Linear” and press ENTER. The
Point Setup menu for Log Linear will be displayed and may require programming the following parameters:
Point Tag
Section 5.6.5.1
Input Scale
Section 5.6.5.2
Output Scale
Section 5.6.5.3 (Lo and Hi Exponents)
Exc. Currents
Section 5.6.5.5
Filter
Section 5.6.5.6
Engineering Units
Section 5.6.5.9
Alarm Setpoints
Section 5.6.5.10
Chart Scale
Section 5.6.5.11
Output Scale - All Log linear current and voltage inputs must be assigned low and high output scale
endpoints. The endpoints are the exponent values (the x in 10
x
) between +25 to -25.
5.6.10 Thermocouple (T/C) Point Types
Several Thermocouple type points are available for use. From the Point Type menu use the UP (
↑) or DOWN
(
↓) Arrow Keys to highlight “T/C” and press ENTER. A list of available thermocouple types is presented. Use
the UP (
↑) or DOWN (↓) Arrow Keys to highlight the desired thermocouple type:
J, K, T, E, R, S, B, C, Ninimo, or Nicro
and press ENTER. The Point Setup menu for Thermocouples will be displayed and may require programming the
following parameters:
Point Tag
Section 5.6.5.1
Decimal fix
Section 5.6.5.4
Filter
Section 5.6.5.6
Compensation
Section 5.6.5.7
Span/Offset
Section 5.6.5.8
Engineering Units
Section 5.6.5.9
Alarm Setpoints
Section 5.6.5.10
Chart Scale
Section 5.6.5.11
5.6.11 Resistance Temperature Detector (RTD)
Several types of RTD’s are available for selection. From the Point Type menu use the UP (
↑) or DOWN (↓)
Arrow Keys to highlight “Rtd” and press ENTER. A list of available RTD types is presented. Use the UP (
↑) or
DOWN (
↓) Arrow Keys to highlight the desired RTD type:
10
Ω Cu, 100Ω PT 385, 100Ω PT 392, 200Ω PT 385, 200Ω PT 392, 120Ω ni, 100Ω ni or 1000Ω ni
and press ENTER. The Point Setup menu for Rtd’s will be displayed and may require programming the
following parameters:
Point Tag
Section 5.6.5.1
Decimal fix
Section 5.6.5.4
Filter
Section 5.6.5.6
Span/Offset
Section 5.6.5.8
Engineering Units
Section 5.6.5.9
Alarm Setpoint
Section 5.6.5.10
Chart Scale
Section 5.6.5.11