Monarch Instrument DC 2000 User Manual
Page 138

Appendix B – Configuring a 4-20 mA input to equal 0 to 150 gpm
Page 4 of 7
You will be prompted with
alarm #?
. Each point has 5
internal alarm set points. You can use the up/down arrow
keys to scroll through 1, 2, 3, 4, or 5. Since this is the first
alarm set point for channel one, select
1
and touch
ENTER
.
The alarm types menu will now be displayed. Using the up/
down arrow keys you can select the type of alarm you wish
to configure. For this example we want to know when the
flow exceeds 120 gpm. Select
Type=high
and touch
ENTER
.
You will next be prompted
contact #?
. If your recorder is
fitted with alarm contact outputs, you can select which
contact will change state when the internal high alarm
activates. Using the up/down arrows you can select 0, 1, 2,
3, 4, 5 or 6. For this example select
2
and touch
ENTER.
Note:
If you do not have relays or do not wish to activate a
relay, select
0
(0 is the default setting) and touch
ENTER
.
A numeric keypad will now be displayed prompting you with
high
→
→
→
→ ←
←
←
←
. Enter
120
and touch
ENTER
.
16.
17.
18.
19.
Using the up/down arrow keys select
Alm limits
and touch
ENTER
.
15.