Appendix A – Configuring a 1-5 Vdc input for a 0-250 psig pressure transducer
Page 2 of 6
The menu containing types of inputs should now be
displayed. Use the up/down arrow keys to select
Linear
and
then touch
ENTER
.
The menu starting with
Point tag
will appear again. Using
the up/down arrow keys select
Input scale
and touch
ENTER
. A numeric keypad will appear with
lo
→
→
→
→ ←
←
←
←
displayed. This is the point that you enter the low range of
your input signal. For this example (1-5 Volts DC) enter
1.00
as the low range and touch
ENTER
.
An alphanumeric keypad will be displayed. This is where
you enter a word or phrase (up to 10 characters*) that
describes this particular point. There are multiple pages of
letters, numbers and symbols that can be used. Use the
PAGE
,
PAGEBK
and
SHIFT
keys to access different
characters. For this example enter the word
INLET
and
touch
ENTER
.
* Only 8 characters will be displayed on the screen although
all ten will be recorded and can be displayed using the
Companion Software
.
The menu displaying types of linear inputs should now
appear. (Selections may appear different from the screen
example to the left.) For this example use the up/down
arrow keys to select the
12.5V
(for 12.5Volt) range then
touch
ENTER
.
The menu starting with
Point tag
will appear. Using the up/
down arrow keys select
Point tag
and touch
ENTER
.
6.
9.
8.
7.
If you are configuring the Recorder for the first time, a menu
having
Setup pt
,
Copy pt
and
Restore pt
will appear. If
you are changing a point that you have already configured,
the menu will have
Modify pt
and
Delete pt
. Depending on
which menu appears, use the up/down arrow keys to select
Setup pt
or
Modify pt
and then touch
ENTER
.
5.